🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 60 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.73%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.08V (0.9%)
Voltage at Load End119.1 VLoss: 0.88 V (372.1 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 60 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A159.93 V (133.28%)0.0 V263.81 V (219.84%)67971.1 WDrop/Amp High
12 AWG3.31 mm²20 A100.5 V (83.75%)19.5 V165.78 V (138.15%)42713.0 WDrop/Amp High
10 AWG5.26 mm²30 A63.24 V (52.7%)56.8 V104.32 V (86.93%)26878.3 WDrop/Amp High
8 AWG8.37 mm²50 A39.74 V (33.12%)80.3 V65.56 V (54.63%)16891.3 WDrop/Amp High
6 AWG13.3 mm²65 A25.01 V (20.84%)95.0 V41.26 V (34.38%)10630.1 WDrop/Amp High
4 AWG21.15 mm²85 A15.73 V (13.11%)104.3 V25.94 V (21.62%)6684.6 WDrop/Amp High
3 AWG26.67 mm²100 A12.47 V (10.39%)107.5 V20.57 V (17.15%)5301.1 WDrop/Amp High
2 AWG33.62 mm²115 A9.89 V (8.25%)110.1 V16.32 V (13.6%)4205.2 WDrop/Amp High
1 AWG42.41 mm²130 A7.84 V (6.54%)112.2 V12.94 V (10.78%)3333.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.22 V (5.18%)113.8 V10.26 V (8.55%)2643.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.93 V (4.11%)115.1 V8.14 V (6.78%)2096.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.91 V (3.26%)116.1 V6.45 V (5.38%)1663.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.1 V (2.59%)116.9 V5.12 V (4.27%)1318.8 WDrop/Amp High
250 kcmil126.7 mm²255 A2.63 V (2.19%)117.4 V4.33 V (3.61%)1115.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.19 V (1.82%)117.8 V3.61 V (3.01%)930.1 WDrop/Amp High
350 kcmil177.3 mm²310 A1.88 V (1.56%)118.1 V3.09 V (2.58%)797.4 WDrop/Amp High
400 kcmil202.7 mm²335 A1.64 V (1.37%)118.4 V2.71 V (2.26%)697.5 WDrop/Amp High
500 kcmil253.4 mm²380 A1.31 V (1.09%)118.7 V2.17 V (1.8%)557.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.09 V (0.91%)118.9 V1.81 V (1.5%)465.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.88 V (0.73%)119.1 V1.44 V (1.2%)372.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.66 V (0.55%)119.3 V1.08 V (0.9%)279.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 60 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 60 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.88V (0.73%) and delivers 119.1V at the load.

What size aluminum wire is required for 425 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.08V (0.9%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.