🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 150 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.71V (2.26%)
Voltage at Load End117.8 VLoss: 2.19 V (930.1 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 150 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A399.83 V (333.19%)0.0 V659.53 V (549.61%)169927.8 WDrop/Amp High
12 AWG3.31 mm²20 A251.25 V (209.38%)0.0 V414.45 V (345.37%)106782.4 WDrop/Amp High
10 AWG5.26 mm²30 A158.11 V (131.76%)0.0 V260.8 V (217.34%)67195.8 WDrop/Amp High
8 AWG8.37 mm²50 A99.36 V (82.8%)20.6 V163.9 V (136.58%)42228.2 WDrop/Amp High
6 AWG13.3 mm²65 A62.53 V (52.11%)57.5 V103.15 V (85.95%)26575.2 WDrop/Amp High
4 AWG21.15 mm²85 A39.32 V (32.77%)80.7 V64.86 V (54.05%)16711.6 WDrop/Amp High
3 AWG26.67 mm²100 A31.18 V (25.99%)88.8 V51.44 V (42.86%)13252.7 WDrop/Amp High
2 AWG33.62 mm²115 A24.74 V (20.61%)95.3 V40.8 V (34.0%)10513.1 WDrop/Amp High
1 AWG42.41 mm²130 A19.61 V (16.34%)100.4 V32.35 V (26.96%)8334.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.55 V (12.96%)104.5 V25.65 V (21.37%)6607.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.33 V (10.28%)107.7 V20.34 V (16.95%)5241.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.78 V (8.15%)110.2 V16.14 V (13.45%)4157.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.76 V (6.46%)112.2 V12.8 V (10.66%)3297.1 WDrop/Amp High
250 kcmil126.7 mm²255 A6.56 V (5.47%)113.4 V10.83 V (9.02%)2789.7 WDrop/Amp High
300 kcmil152.0 mm²285 A5.47 V (4.56%)114.5 V9.03 V (7.52%)2325.3 WDrop/Amp High
350 kcmil177.3 mm²310 A4.69 V (3.91%)115.3 V7.74 V (6.45%)1993.5 WDrop/Amp High
400 kcmil202.7 mm²335 A4.1 V (3.42%)115.9 V6.77 V (5.64%)1743.7 WDrop/Amp High
500 kcmil253.4 mm²380 A3.28 V (2.73%)116.7 V5.41 V (4.51%)1394.8 WDrop/Amp High
600 kcmil304.0 mm²420 A2.74 V (2.28%)117.3 V4.51 V (3.76%)1162.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.19 V (1.82%)117.8 V3.61 V (3.01%)930.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.64 V (1.37%)118.4 V2.71 V (2.26%)697.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 150 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 150 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.19V (1.82%) and delivers 117.8V at the load.

What size aluminum wire is required for 425 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.71V (2.26%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.