🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 200 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.22%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.61V (1.5%)
Voltage at Load End237.1 VLoss: 2.92 V (1240.2 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 200 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A533.11 V (222.13%)0.0 V879.38 V (366.41%)226570.4 WDrop/Amp High
12 AWG3.31 mm²20 A335.0 V (139.58%)0.0 V552.6 V (230.25%)142376.6 WDrop/Amp High
10 AWG5.26 mm²30 A210.81 V (87.84%)29.2 V347.74 V (144.89%)89594.4 WDrop/Amp High
8 AWG8.37 mm²50 A132.48 V (55.2%)107.5 V218.53 V (91.05%)56304.2 WDrop/Amp High
6 AWG13.3 mm²65 A83.37 V (34.74%)156.6 V137.53 V (57.3%)35433.6 WDrop/Amp High
4 AWG21.15 mm²85 A52.43 V (21.85%)187.6 V86.48 V (36.03%)22282.1 WDrop/Amp High
3 AWG26.67 mm²100 A41.58 V (17.32%)198.4 V68.58 V (28.58%)17670.3 WDrop/Amp High
2 AWG33.62 mm²115 A32.98 V (13.74%)207.0 V54.41 V (22.67%)14017.4 WDrop/Amp High
1 AWG42.41 mm²130 A26.15 V (10.89%)213.9 V43.13 V (17.97%)11112.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.73 V (8.64%)219.3 V34.2 V (14.25%)8810.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.44 V (6.85%)223.6 V27.13 V (11.3%)6989.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.04 V (5.43%)227.0 V21.52 V (8.97%)5543.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.34 V (4.31%)229.7 V17.06 V (7.11%)4396.1 WDrop/Amp High
250 kcmil126.7 mm²255 A8.75 V (3.65%)231.2 V14.44 V (6.02%)3719.5 WDrop/Amp High
300 kcmil152.0 mm²285 A7.3 V (3.04%)232.7 V12.03 V (5.01%)3100.4 WDrop/Amp High
350 kcmil177.3 mm²310 A6.25 V (2.61%)233.7 V10.32 V (4.3%)2658.0 WDrop/Amp High
400 kcmil202.7 mm²335 A5.47 V (2.28%)234.5 V9.02 V (3.76%)2324.9 WDrop/Amp High
500 kcmil253.4 mm²380 A4.38 V (1.82%)235.6 V7.22 V (3.01%)1859.8 WDrop/Amp High
600 kcmil304.0 mm²420 A3.65 V (1.52%)236.4 V6.02 V (2.51%)1550.2 WDrop/Amp High
750 kcmil380.0 mm²475 A2.92 V (1.22%)237.1 V4.81 V (2.01%)1240.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.19 V (0.91%)237.8 V3.61 V (1.5%)930.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 200 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 200 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.92V (1.22%) and delivers 237.1V at the load.

What size aluminum wire is required for 425 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.61V (1.5%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.