⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 200 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.05%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.13V (1.3%)
Voltage at Load End237.5 VLoss: 2.53 V (1860.3 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 200 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A461.68 V (192.37%)0.0 V761.56 V (317.32%)339855.7 WDrop/Amp High
12 AWG3.31 mm²20 A290.12 V (120.88%)0.0 V478.57 V (199.4%)213564.9 WDrop/Amp High
10 AWG5.26 mm²30 A182.57 V (76.07%)57.4 V301.15 V (125.48%)134391.6 WDrop/Amp High
8 AWG8.37 mm²50 A114.73 V (47.8%)125.3 V189.25 V (78.86%)84456.4 WDrop/Amp High
6 AWG13.3 mm²65 A72.2 V (30.08%)167.8 V119.1 V (49.63%)53150.4 WDrop/Amp High
4 AWG21.15 mm²85 A45.4 V (18.92%)194.6 V74.9 V (31.21%)33423.2 WDrop/Amp High
3 AWG26.67 mm²100 A36.01 V (15.0%)204.0 V59.39 V (24.75%)26505.4 WDrop/Amp High
2 AWG33.62 mm²115 A28.56 V (11.9%)211.4 V47.12 V (19.63%)21026.2 WDrop/Amp High
1 AWG42.41 mm²130 A22.64 V (9.43%)217.4 V37.35 V (15.56%)16668.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.95 V (7.48%)222.0 V29.61 V (12.34%)13215.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.24 V (5.93%)225.8 V23.49 V (9.79%)10483.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.3 V (4.71%)228.7 V18.63 V (7.76%)8315.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.96 V (3.73%)231.0 V14.78 V (6.16%)6594.2 WDrop/Amp High
250 kcmil126.7 mm²255 A7.58 V (3.16%)232.4 V12.5 V (5.21%)5579.3 WDrop/Amp High
300 kcmil152.0 mm²285 A6.32 V (2.63%)233.7 V10.42 V (4.34%)4650.7 WDrop/Amp High
350 kcmil177.3 mm²310 A5.42 V (2.26%)234.6 V8.93 V (3.72%)3987.0 WDrop/Amp High
400 kcmil202.7 mm²335 A4.74 V (1.97%)235.3 V7.81 V (3.26%)3487.4 WDrop/Amp High
500 kcmil253.4 mm²380 A3.79 V (1.58%)236.2 V6.25 V (2.6%)2789.7 WDrop/Amp High
600 kcmil304.0 mm²420 A3.16 V (1.32%)236.8 V5.21 V (2.17%)2325.3 WDrop/Amp High
750 kcmil380.0 mm²475 A2.53 V (1.05%)237.5 V4.17 V (1.74%)1860.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.9 V (0.79%)238.1 V3.13 V (1.3%)1395.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 200 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 200 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.53V (1.05%) and delivers 237.5V at the load.

What size aluminum wire is required for 425 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.13V (1.3%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.