⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 225 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.18%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.52V (1.47%)
Voltage at Load End237.2 VLoss: 2.84 V (2092.8 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A519.39 V (216.41%)0.0 V856.76 V (356.98%)382337.6 WDrop/Amp High
12 AWG3.31 mm²20 A326.39 V (135.99%)0.0 V538.39 V (224.33%)240260.5 WDrop/Amp High
10 AWG5.26 mm²30 A205.39 V (85.58%)34.6 V338.79 V (141.16%)151190.5 WDrop/Amp High
8 AWG8.37 mm²50 A129.07 V (53.78%)110.9 V212.91 V (88.71%)95013.4 WDrop/Amp High
6 AWG13.3 mm²65 A81.23 V (33.85%)158.8 V133.99 V (55.83%)59794.2 WDrop/Amp High
4 AWG21.15 mm²85 A51.08 V (21.28%)188.9 V84.26 V (35.11%)37601.1 WDrop/Amp High
3 AWG26.67 mm²100 A40.51 V (16.88%)199.5 V66.82 V (27.84%)29818.6 WDrop/Amp High
2 AWG33.62 mm²115 A32.13 V (13.39%)207.9 V53.01 V (22.09%)23654.4 WDrop/Amp High
1 AWG42.41 mm²130 A25.47 V (10.61%)214.5 V42.02 V (17.51%)18751.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.2 V (8.42%)219.8 V33.32 V (13.88%)14867.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.02 V (6.68%)224.0 V26.43 V (11.01%)11793.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.71 V (5.3%)227.3 V20.96 V (8.73%)9354.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.08 V (4.2%)229.9 V16.62 V (6.93%)7418.5 WDrop/Amp High
250 kcmil126.7 mm²255 A8.53 V (3.55%)231.5 V14.07 V (5.86%)6276.7 WDrop/Amp High
300 kcmil152.0 mm²285 A7.11 V (2.96%)232.9 V11.72 V (4.89%)5232.0 WDrop/Amp High
350 kcmil177.3 mm²310 A6.09 V (2.54%)233.9 V10.05 V (4.19%)4485.4 WDrop/Amp High
400 kcmil202.7 mm²335 A5.33 V (2.22%)234.7 V8.79 V (3.66%)3923.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.26 V (1.78%)235.7 V7.03 V (2.93%)3138.4 WDrop/Amp High
600 kcmil304.0 mm²420 A3.55 V (1.48%)236.4 V5.86 V (2.44%)2616.0 WDrop/Amp High
750 kcmil380.0 mm²475 A2.84 V (1.18%)237.2 V4.69 V (1.95%)2092.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.13 V (0.89%)237.9 V3.52 V (1.47%)1569.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 225 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.84V (1.18%) and delivers 237.2V at the load.

What size aluminum wire is required for 425 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.52V (1.47%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.