🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 250 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)8× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.85%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.51V (37.6%)
Voltage at Load End11.7 VLoss: 0.34 V (145.3 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 250 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A666.38 V (5553.2%)0.0 V1099.22 V (9160.18%)283213.1 WDrop/Amp High
12 AWG3.31 mm²20 A418.75 V (3489.62%)0.0 V690.75 V (5756.25%)177970.7 WDrop/Amp High
10 AWG5.26 mm²30 A263.51 V (2195.94%)0.0 V434.67 V (3622.28%)111993.0 WDrop/Amp High
8 AWG8.37 mm²50 A165.6 V (1380.01%)0.0 V273.16 V (2276.36%)70380.3 WDrop/Amp High
6 AWG13.3 mm²65 A104.22 V (868.47%)0.0 V171.91 V (1432.57%)44292.0 WDrop/Amp High
4 AWG21.15 mm²85 A65.54 V (546.13%)0.0 V108.1 V (900.86%)27852.6 WDrop/Amp High
3 AWG26.67 mm²100 A51.97 V (433.1%)0.0 V85.73 V (714.4%)22087.9 WDrop/Amp High
2 AWG33.62 mm²115 A41.23 V (343.56%)0.0 V68.01 V (566.72%)17521.8 WDrop/Amp High
1 AWG42.41 mm²130 A32.68 V (272.36%)0.0 V53.91 V (449.26%)13890.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.91 V (215.94%)0.0 V42.74 V (356.2%)11013.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.56 V (171.3%)0.0 V33.91 V (282.56%)8736.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.3 V (135.87%)0.0 V26.9 V (224.13%)6929.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.93 V (107.75%)0.0 V21.33 V (177.73%)5495.2 WDrop/Amp High
250 kcmil126.7 mm²255 A10.94 V (91.17%)1.1 V18.05 V (150.38%)4649.4 WDrop/Amp High
300 kcmil152.0 mm²285 A9.12 V (75.99%)2.9 V15.04 V (125.35%)3875.5 WDrop/Amp High
350 kcmil177.3 mm²310 A7.82 V (65.15%)4.2 V12.9 V (107.46%)3322.5 WDrop/Amp High
400 kcmil202.7 mm²335 A6.84 V (56.98%)5.2 V11.28 V (94.0%)2906.2 WDrop/Amp High
500 kcmil253.4 mm²380 A5.47 V (45.58%)6.5 V9.02 V (75.19%)2324.7 WDrop/Amp High
600 kcmil304.0 mm²420 A4.56 V (38.0%)7.4 V7.52 V (62.67%)1937.8 WDrop/Amp High
750 kcmil380.0 mm²475 A3.65 V (30.4%)8.4 V6.02 V (50.14%)1550.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.74 V (22.8%)9.3 V4.51 V (37.6%)1162.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 250 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 250 feet one-way at 12V (DC), you need 8× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.85%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.51V (37.6%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.