🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 20 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.43%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.36V (3.01%)
Voltage at Load End11.7 VLoss: 0.29 V (124.0 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 20 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A53.31 V (444.26%)0.0 V87.94 V (732.81%)22657.0 WDrop/Amp High
12 AWG3.31 mm²20 A33.5 V (279.17%)0.0 V55.26 V (460.5%)14237.7 WDrop/Amp High
10 AWG5.26 mm²30 A21.08 V (175.68%)0.0 V34.77 V (289.78%)8959.4 WDrop/Amp High
8 AWG8.37 mm²50 A13.25 V (110.4%)0.0 V21.85 V (182.11%)5630.4 WDrop/Amp High
6 AWG13.3 mm²65 A8.34 V (69.48%)3.7 V13.75 V (114.61%)3543.4 WDrop/Amp High
4 AWG21.15 mm²85 A5.24 V (43.69%)6.8 V8.65 V (72.07%)2228.2 WDrop/Amp High
3 AWG26.67 mm²100 A4.16 V (34.65%)7.8 V6.86 V (57.15%)1767.0 WDrop/Amp High
2 AWG33.62 mm²115 A3.3 V (27.49%)8.7 V5.44 V (45.34%)1401.7 WDrop/Amp High
1 AWG42.41 mm²130 A2.61 V (21.79%)9.4 V4.31 V (35.94%)1111.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.07 V (17.28%)9.9 V3.42 V (28.5%)881.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.64 V (13.7%)10.4 V2.71 V (22.6%)698.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.3 V (10.87%)10.7 V2.15 V (17.93%)554.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.03 V (8.62%)11.0 V1.71 V (14.22%)439.6 WDrop/Amp High
250 kcmil126.7 mm²255 A0.88 V (7.29%)11.1 V1.44 V (12.03%)372.0 WDrop/Amp High
300 kcmil152.0 mm²285 A0.73 V (6.08%)11.3 V1.2 V (10.03%)310.0 WDrop/Amp High
350 kcmil177.3 mm²310 A0.63 V (5.21%)11.4 V1.03 V (8.6%)265.8 WDrop/Amp High
400 kcmil202.7 mm²335 A0.55 V (4.56%)11.5 V0.9 V (7.52%)232.5 WDrop/Amp High
500 kcmil253.4 mm²380 A0.44 V (3.65%)11.6 V0.72 V (6.02%)186.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.36 V (3.04%)11.6 V0.6 V (5.01%)155.0 WDrop/Amp High
750 kcmil380.0 mm²475 A0.29 V (2.43%)11.7 V0.48 V (4.01%)124.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.22 V (1.82%)11.8 V0.36 V (3.01%)93.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 20 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 20 feet one-way at 12V (DC), you need 750 kcmil copper wire. This produces a voltage drop of 0.29V (2.43%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.36V (3.01%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.