🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 30 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.74%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.54V (4.51%)
Voltage at Load End11.7 VLoss: 0.33 V (139.5 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 30 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A79.97 V (666.38%)0.0 V131.91 V (1099.22%)33985.6 WDrop/Amp High
12 AWG3.31 mm²20 A50.25 V (418.75%)0.0 V82.89 V (690.75%)21356.5 WDrop/Amp High
10 AWG5.26 mm²30 A31.62 V (263.51%)0.0 V52.16 V (434.67%)13439.2 WDrop/Amp High
8 AWG8.37 mm²50 A19.87 V (165.6%)0.0 V32.78 V (273.16%)8445.6 WDrop/Amp High
6 AWG13.3 mm²65 A12.51 V (104.22%)0.0 V20.63 V (171.91%)5315.0 WDrop/Amp High
4 AWG21.15 mm²85 A7.86 V (65.54%)4.1 V12.97 V (108.1%)3342.3 WDrop/Amp High
3 AWG26.67 mm²100 A6.24 V (51.97%)5.8 V10.29 V (85.73%)2650.5 WDrop/Amp High
2 AWG33.62 mm²115 A4.95 V (41.23%)7.1 V8.16 V (68.01%)2102.6 WDrop/Amp High
1 AWG42.41 mm²130 A3.92 V (32.68%)8.1 V6.47 V (53.91%)1666.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.11 V (25.91%)8.9 V5.13 V (42.74%)1321.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.47 V (20.56%)9.5 V4.07 V (33.91%)1048.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.96 V (16.3%)10.0 V3.23 V (26.9%)831.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.55 V (12.93%)10.4 V2.56 V (21.33%)659.4 WDrop/Amp High
250 kcmil126.7 mm²255 A1.31 V (10.94%)10.7 V2.17 V (18.05%)557.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.09 V (9.12%)10.9 V1.81 V (15.04%)465.1 WDrop/Amp High
350 kcmil177.3 mm²310 A0.94 V (7.82%)11.1 V1.55 V (12.9%)398.7 WDrop/Amp High
400 kcmil202.7 mm²335 A0.82 V (6.84%)11.2 V1.35 V (11.28%)348.7 WDrop/Amp High
500 kcmil253.4 mm²380 A0.66 V (5.47%)11.3 V1.08 V (9.02%)279.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.55 V (4.56%)11.5 V0.9 V (7.52%)232.5 WDrop/Amp High
750 kcmil380.0 mm²475 A0.44 V (3.65%)11.6 V0.72 V (6.02%)186.0 W~ ≤5%
1000 kcmil506.7 mm²545 A0.33 V (2.74%)11.7 V0.54 V (4.51%)139.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 30 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 30 feet one-way at 12V (DC), you need 1000 kcmil copper wire. This produces a voltage drop of 0.33V (2.74%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.54V (4.51%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.