🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 80 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.43%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.44V (12.03%)
Voltage at Load End11.7 VLoss: 0.29 V (124.0 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 80 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A213.24 V (1777.02%)0.0 V351.75 V (2931.26%)90628.2 WDrop/Amp High
12 AWG3.31 mm²20 A134.0 V (1116.68%)0.0 V221.04 V (1842.0%)56950.6 WDrop/Amp High
10 AWG5.26 mm²30 A84.32 V (702.7%)0.0 V139.1 V (1159.13%)35837.8 WDrop/Amp High
8 AWG8.37 mm²50 A52.99 V (441.6%)0.0 V87.41 V (728.44%)22521.7 WDrop/Amp High
6 AWG13.3 mm²65 A33.35 V (277.91%)0.0 V55.01 V (458.42%)14173.4 WDrop/Amp High
4 AWG21.15 mm²85 A20.97 V (174.76%)0.0 V34.59 V (288.27%)8912.8 WDrop/Amp High
3 AWG26.67 mm²100 A16.63 V (138.59%)0.0 V27.43 V (228.61%)7068.1 WDrop/Amp High
2 AWG33.62 mm²115 A13.19 V (109.94%)0.0 V21.76 V (181.35%)5607.0 WDrop/Amp High
1 AWG42.41 mm²130 A10.46 V (87.15%)1.5 V17.25 V (143.76%)4444.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.29 V (69.1%)3.7 V13.68 V (113.98%)3524.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.58 V (54.82%)5.4 V10.85 V (90.42%)2795.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.22 V (43.48%)6.8 V8.61 V (71.72%)2217.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.14 V (34.48%)7.9 V6.83 V (56.88%)1758.5 WDrop/Amp High
250 kcmil126.7 mm²255 A3.5 V (29.17%)8.5 V5.77 V (48.12%)1487.8 WDrop/Amp High
300 kcmil152.0 mm²285 A2.92 V (24.32%)9.1 V4.81 V (40.11%)1240.2 WDrop/Amp High
350 kcmil177.3 mm²310 A2.5 V (20.85%)9.5 V4.13 V (34.39%)1063.2 WDrop/Amp High
400 kcmil202.7 mm²335 A2.19 V (18.23%)9.8 V3.61 V (30.08%)930.0 WDrop/Amp High
500 kcmil253.4 mm²380 A1.75 V (14.59%)10.2 V2.89 V (24.06%)743.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.46 V (12.16%)10.5 V2.41 V (20.06%)620.1 WDrop/Amp High
750 kcmil380.0 mm²475 A1.17 V (9.73%)10.8 V1.93 V (16.04%)496.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.88 V (7.29%)11.1 V1.44 V (12.03%)372.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 80 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 80 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.29V (2.43%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.44V (12.03%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.