⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 40 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.72V (6.02%)
Voltage at Load End11.8 VLoss: 0.22 V (93.0 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 40 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A106.62 V (888.51%)0.0 V175.88 V (1465.63%)45314.1 WDrop/Amp High
12 AWG3.31 mm²20 A67.0 V (558.34%)0.0 V110.52 V (921.0%)28475.3 WDrop/Amp High
10 AWG5.26 mm²30 A42.16 V (351.35%)0.0 V69.55 V (579.56%)17918.9 WDrop/Amp High
8 AWG8.37 mm²50 A26.5 V (220.8%)0.0 V43.71 V (364.22%)11260.8 WDrop/Amp High
6 AWG13.3 mm²65 A16.67 V (138.96%)0.0 V27.51 V (229.21%)7086.7 WDrop/Amp High
4 AWG21.15 mm²85 A10.49 V (87.38%)1.5 V17.3 V (144.14%)4456.4 WDrop/Amp High
3 AWG26.67 mm²100 A8.32 V (69.3%)3.7 V13.72 V (114.3%)3534.1 WDrop/Amp High
2 AWG33.62 mm²115 A6.6 V (54.97%)5.4 V10.88 V (90.68%)2803.5 WDrop/Amp High
1 AWG42.41 mm²130 A5.23 V (43.58%)6.8 V8.63 V (71.88%)2222.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.15 V (34.55%)7.9 V6.84 V (56.99%)1762.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.29 V (27.41%)8.7 V5.43 V (45.21%)1397.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.61 V (21.74%)9.4 V4.3 V (35.86%)1108.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.07 V (17.24%)9.9 V3.41 V (28.44%)879.2 WDrop/Amp High
250 kcmil126.7 mm²255 A1.75 V (14.59%)10.2 V2.89 V (24.06%)743.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.46 V (12.16%)10.5 V2.41 V (20.06%)620.1 WDrop/Amp High
350 kcmil177.3 mm²310 A1.25 V (10.42%)10.7 V2.06 V (17.19%)531.6 WDrop/Amp High
400 kcmil202.7 mm²335 A1.09 V (9.12%)10.9 V1.8 V (15.04%)465.0 WDrop/Amp High
500 kcmil253.4 mm²380 A0.88 V (7.29%)11.1 V1.44 V (12.03%)372.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.73 V (6.08%)11.3 V1.2 V (10.03%)310.0 WDrop/Amp High
750 kcmil380.0 mm²475 A0.58 V (4.86%)11.4 V0.96 V (8.02%)248.0 W~ ≤5%
1000 kcmil506.7 mm²545 A0.44 V (3.65%)11.6 V0.72 V (6.02%)186.0 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 40 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 40 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.22V (1.82%) and delivers 11.8V at the load.

What size aluminum wire is required for 425 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.72V (6.02%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.