425 Amp Wire Size at 150 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.74%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.71V (22.56%)
Voltage at Load End11.7 VLoss: 0.33 V (139.5 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 150 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A399.83 V (3331.92%)0.0 V659.53 V (5496.11%)169927.8 WDrop/Amp High
12 AWG3.31 mm²20 A251.25 V (2093.77%)0.0 V414.45 V (3453.75%)106782.4 WDrop/Amp High
10 AWG5.26 mm²30 A158.11 V (1317.56%)0.0 V260.8 V (2173.37%)67195.8 WDrop/Amp High
8 AWG8.37 mm²50 A99.36 V (828.0%)0.0 V163.9 V (1365.82%)42228.2 WDrop/Amp High
6 AWG13.3 mm²65 A62.53 V (521.08%)0.0 V103.15 V (859.54%)26575.2 WDrop/Amp High
4 AWG21.15 mm²85 A39.32 V (327.68%)0.0 V64.86 V (540.52%)16711.6 WDrop/Amp High
3 AWG26.67 mm²100 A31.18 V (259.86%)0.0 V51.44 V (428.64%)13252.7 WDrop/Amp High
2 AWG33.62 mm²115 A24.74 V (206.14%)0.0 V40.8 V (340.03%)10513.1 WDrop/Amp High
1 AWG42.41 mm²130 A19.61 V (163.41%)0.0 V32.35 V (269.56%)8334.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.55 V (129.56%)0.0 V25.65 V (213.72%)6607.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.33 V (102.78%)0.0 V20.34 V (169.54%)5241.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.78 V (81.52%)2.2 V16.14 V (134.48%)4157.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.76 V (64.65%)4.2 V12.8 V (106.64%)3297.1 WDrop/Amp High
250 kcmil126.7 mm²255 A6.56 V (54.7%)5.4 V10.83 V (90.23%)2789.7 WDrop/Amp High
300 kcmil152.0 mm²285 A5.47 V (45.59%)6.5 V9.03 V (75.21%)2325.3 WDrop/Amp High
350 kcmil177.3 mm²310 A4.69 V (39.09%)7.3 V7.74 V (64.48%)1993.5 WDrop/Amp High
400 kcmil202.7 mm²335 A4.1 V (34.19%)7.9 V6.77 V (56.4%)1743.7 WDrop/Amp High
500 kcmil253.4 mm²380 A3.28 V (27.35%)8.7 V5.41 V (45.11%)1394.8 WDrop/Amp High
600 kcmil304.0 mm²420 A2.74 V (22.8%)9.3 V4.51 V (37.6%)1162.7 WDrop/Amp High
750 kcmil380.0 mm²475 A2.19 V (18.24%)9.8 V3.61 V (30.08%)930.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.64 V (13.68%)10.4 V2.71 V (22.56%)697.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 150 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 150 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.74%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.71V (22.56%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.