🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 60 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.73%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.08V (9.02%)
Voltage at Load End11.7 VLoss: 0.33 V (139.5 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 60 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A159.93 V (1332.77%)0.0 V263.81 V (2198.44%)67971.1 WDrop/Amp High
12 AWG3.31 mm²20 A100.5 V (837.51%)0.0 V165.78 V (1381.5%)42713.0 WDrop/Amp High
10 AWG5.26 mm²30 A63.24 V (527.03%)0.0 V104.32 V (869.35%)26878.3 WDrop/Amp High
8 AWG8.37 mm²50 A39.74 V (331.2%)0.0 V65.56 V (546.33%)16891.3 WDrop/Amp High
6 AWG13.3 mm²65 A25.01 V (208.43%)0.0 V41.26 V (343.82%)10630.1 WDrop/Amp High
4 AWG21.15 mm²85 A15.73 V (131.07%)0.0 V25.94 V (216.21%)6684.6 WDrop/Amp High
3 AWG26.67 mm²100 A12.47 V (103.94%)0.0 V20.57 V (171.46%)5301.1 WDrop/Amp High
2 AWG33.62 mm²115 A9.89 V (82.46%)2.1 V16.32 V (136.01%)4205.2 WDrop/Amp High
1 AWG42.41 mm²130 A7.84 V (65.37%)4.2 V12.94 V (107.82%)3333.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.22 V (51.83%)5.8 V10.26 V (85.49%)2643.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.93 V (41.11%)7.1 V8.14 V (67.81%)2096.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.91 V (32.61%)8.1 V6.45 V (53.79%)1663.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.1 V (25.86%)8.9 V5.12 V (42.66%)1318.8 WDrop/Amp High
250 kcmil126.7 mm²255 A2.63 V (21.88%)9.4 V4.33 V (36.09%)1115.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.19 V (18.24%)9.8 V3.61 V (30.08%)930.1 WDrop/Amp High
350 kcmil177.3 mm²310 A1.88 V (15.64%)10.1 V3.09 V (25.79%)797.4 WDrop/Amp High
400 kcmil202.7 mm²335 A1.64 V (13.68%)10.4 V2.71 V (22.56%)697.5 WDrop/Amp High
500 kcmil253.4 mm²380 A1.31 V (10.94%)10.7 V2.17 V (18.05%)557.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.09 V (9.12%)10.9 V1.81 V (15.04%)465.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.88 V (7.3%)11.1 V1.44 V (12.03%)372.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.66 V (5.47%)11.3 V1.08 V (9.02%)279.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 60 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 60 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.73%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.08V (9.02%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.