🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 75 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.35V (11.28%)
Voltage at Load End11.7 VLoss: 0.27 V (116.3 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 75 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A199.92 V (1665.96%)0.0 V329.77 V (2748.05%)84963.9 WDrop/Amp High
12 AWG3.31 mm²20 A125.63 V (1046.89%)0.0 V207.22 V (1726.87%)53391.2 WDrop/Amp High
10 AWG5.26 mm²30 A79.05 V (658.78%)0.0 V130.4 V (1086.68%)33597.9 WDrop/Amp High
8 AWG8.37 mm²50 A49.68 V (414.0%)0.0 V81.95 V (682.91%)21114.1 WDrop/Amp High
6 AWG13.3 mm²65 A31.26 V (260.54%)0.0 V51.57 V (429.77%)13287.6 WDrop/Amp High
4 AWG21.15 mm²85 A19.66 V (163.84%)0.0 V32.43 V (270.26%)8355.8 WDrop/Amp High
3 AWG26.67 mm²100 A15.59 V (129.93%)0.0 V25.72 V (214.32%)6626.4 WDrop/Amp High
2 AWG33.62 mm²115 A12.37 V (103.07%)0.0 V20.4 V (170.02%)5256.5 WDrop/Amp High
1 AWG42.41 mm²130 A9.8 V (81.71%)2.2 V16.17 V (134.78%)4167.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.77 V (64.78%)4.2 V12.82 V (106.86%)3303.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.17 V (51.39%)5.8 V10.17 V (84.77%)2620.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.89 V (40.76%)7.1 V8.07 V (67.24%)2078.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.88 V (32.32%)8.1 V6.4 V (53.32%)1648.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.28 V (27.35%)8.7 V5.41 V (45.11%)1394.8 WDrop/Amp High
300 kcmil152.0 mm²285 A2.74 V (22.8%)9.3 V4.51 V (37.6%)1162.7 WDrop/Amp High
350 kcmil177.3 mm²310 A2.35 V (19.54%)9.7 V3.87 V (32.24%)996.8 WDrop/Amp High
400 kcmil202.7 mm²335 A2.05 V (17.1%)9.9 V3.38 V (28.2%)871.9 WDrop/Amp High
500 kcmil253.4 mm²380 A1.64 V (13.67%)10.4 V2.71 V (22.56%)697.4 WDrop/Amp High
600 kcmil304.0 mm²420 A1.37 V (11.4%)10.6 V2.26 V (18.8%)581.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.09 V (9.12%)10.9 V1.81 V (15.04%)465.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.82 V (6.84%)11.2 V1.35 V (11.28%)348.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 75 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 75 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.27V (2.28%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.35V (11.28%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.