🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 50 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.9V (7.52%)
Voltage at Load End11.7 VLoss: 0.28 V (116.2 W)
Power & Breaker (125%)5.1 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 50 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A133.28 V (1110.64%)0.0 V219.84 V (1832.04%)56642.6 WDrop/Amp High
12 AWG3.31 mm²20 A83.75 V (697.92%)0.0 V138.15 V (1151.25%)35594.1 WDrop/Amp High
10 AWG5.26 mm²30 A52.7 V (439.19%)0.0 V86.93 V (724.46%)22398.6 WDrop/Amp High
8 AWG8.37 mm²50 A33.12 V (276.0%)0.0 V54.63 V (455.27%)14076.1 WDrop/Amp High
6 AWG13.3 mm²65 A20.84 V (173.69%)0.0 V34.38 V (286.51%)8858.4 WDrop/Amp High
4 AWG21.15 mm²85 A13.11 V (109.23%)0.0 V21.62 V (180.17%)5570.5 WDrop/Amp High
3 AWG26.67 mm²100 A10.39 V (86.62%)1.6 V17.15 V (142.88%)4417.6 WDrop/Amp High
2 AWG33.62 mm²115 A8.25 V (68.71%)3.8 V13.6 V (113.34%)3504.4 WDrop/Amp High
1 AWG42.41 mm²130 A6.54 V (54.47%)5.5 V10.78 V (89.85%)2778.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.18 V (43.19%)6.8 V8.55 V (71.24%)2202.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.11 V (34.26%)7.9 V6.78 V (56.51%)1747.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.26 V (27.17%)8.7 V5.38 V (44.83%)1385.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.59 V (21.55%)9.4 V4.27 V (35.55%)1099.0 WDrop/Amp High
250 kcmil126.7 mm²255 A2.19 V (18.23%)9.8 V3.61 V (30.08%)929.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.82 V (15.2%)10.2 V3.01 V (25.07%)775.1 WDrop/Amp High
350 kcmil177.3 mm²310 A1.56 V (13.03%)10.4 V2.58 V (21.49%)664.5 WDrop/Amp High
400 kcmil202.7 mm²335 A1.37 V (11.4%)10.6 V2.26 V (18.8%)581.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.09 V (9.12%)10.9 V1.8 V (15.04%)464.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.91 V (7.6%)11.1 V1.5 V (12.53%)387.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.73 V (6.08%)11.3 V1.2 V (10.03%)310.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.55 V (4.56%)11.5 V0.9 V (7.52%)232.5 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 50 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 50 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.28V (2.28%) and delivers 11.7V at the load.

What size aluminum wire is required for 425 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.9V (7.52%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.