⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 250 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.52%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.91V (1.88%)
Voltage at Load End204.8 VLoss: 3.16 V (2325.3 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 250 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A577.11 V (277.45%)0.0 V951.95 V (457.67%)424819.6 WDrop/Amp High
12 AWG3.31 mm²20 A362.65 V (174.35%)0.0 V598.21 V (287.6%)266956.1 WDrop/Amp High
10 AWG5.26 mm²30 A228.21 V (109.72%)0.0 V376.44 V (180.98%)167989.5 WDrop/Amp High
8 AWG8.37 mm²50 A143.41 V (68.95%)64.6 V236.57 V (113.73%)105570.5 WDrop/Amp High
6 AWG13.3 mm²65 A90.25 V (43.39%)117.7 V148.88 V (71.58%)66437.9 WDrop/Amp High
4 AWG21.15 mm²85 A56.76 V (27.29%)151.2 V93.62 V (45.01%)41778.9 WDrop/Amp High
3 AWG26.67 mm²100 A45.01 V (21.64%)163.0 V74.24 V (35.69%)33131.8 WDrop/Amp High
2 AWG33.62 mm²115 A35.7 V (17.17%)172.3 V58.9 V (28.32%)26282.7 WDrop/Amp High
1 AWG42.41 mm²130 A28.3 V (13.61%)179.7 V46.69 V (22.45%)20835.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A22.44 V (10.79%)185.6 V37.02 V (17.8%)16519.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.8 V (8.56%)190.2 V29.36 V (14.12%)13104.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.12 V (6.79%)193.9 V23.29 V (11.2%)10394.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.2 V (5.38%)196.8 V18.47 V (8.88%)8242.8 WDrop/Amp High
250 kcmil126.7 mm²255 A9.47 V (4.55%)198.5 V15.63 V (7.51%)6974.1 WDrop/Amp High
300 kcmil152.0 mm²285 A7.9 V (3.8%)200.1 V13.03 V (6.26%)5813.3 WDrop/Amp High
350 kcmil177.3 mm²310 A6.77 V (3.25%)201.2 V11.17 V (5.37%)4983.8 WDrop/Amp High
400 kcmil202.7 mm²335 A5.92 V (2.85%)202.1 V9.77 V (4.7%)4359.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.74 V (2.28%)203.3 V7.81 V (3.76%)3487.1 WDrop/Amp High
600 kcmil304.0 mm²420 A3.95 V (1.9%)204.1 V6.51 V (3.13%)2906.7 WDrop/Amp High
750 kcmil380.0 mm²475 A3.16 V (1.52%)204.8 V5.21 V (2.51%)2325.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.37 V (1.14%)205.6 V3.91 V (1.88%)1743.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 250 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 250 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.16V (1.52%) and delivers 204.8V at the load.

What size aluminum wire is required for 425 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.91V (1.88%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.