🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 250 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.52%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.51V (1.88%)
Voltage at Load End236.4 VLoss: 3.65 V (1550.2 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A666.38 V (277.66%)0.0 V1099.22 V (458.01%)283213.1 WDrop/Amp High
12 AWG3.31 mm²20 A418.75 V (174.48%)0.0 V690.75 V (287.81%)177970.7 WDrop/Amp High
10 AWG5.26 mm²30 A263.51 V (109.8%)0.0 V434.67 V (181.11%)111993.0 WDrop/Amp High
8 AWG8.37 mm²50 A165.6 V (69.0%)74.4 V273.16 V (113.82%)70380.3 WDrop/Amp High
6 AWG13.3 mm²65 A104.22 V (43.42%)135.8 V171.91 V (71.63%)44292.0 WDrop/Amp High
4 AWG21.15 mm²85 A65.54 V (27.31%)174.5 V108.1 V (45.04%)27852.6 WDrop/Amp High
3 AWG26.67 mm²100 A51.97 V (21.65%)188.0 V85.73 V (35.72%)22087.9 WDrop/Amp High
2 AWG33.62 mm²115 A41.23 V (17.18%)198.8 V68.01 V (28.34%)17521.8 WDrop/Amp High
1 AWG42.41 mm²130 A32.68 V (13.62%)207.3 V53.91 V (22.46%)13890.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.91 V (10.8%)214.1 V42.74 V (17.81%)11013.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.56 V (8.56%)219.4 V33.91 V (14.13%)8736.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.3 V (6.79%)223.7 V26.9 V (11.21%)6929.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.93 V (5.39%)227.1 V21.33 V (8.89%)5495.2 WDrop/Amp High
250 kcmil126.7 mm²255 A10.94 V (4.56%)229.1 V18.05 V (7.52%)4649.4 WDrop/Amp High
300 kcmil152.0 mm²285 A9.12 V (3.8%)230.9 V15.04 V (6.27%)3875.5 WDrop/Amp High
350 kcmil177.3 mm²310 A7.82 V (3.26%)232.2 V12.9 V (5.37%)3322.5 WDrop/Amp High
400 kcmil202.7 mm²335 A6.84 V (2.85%)233.2 V11.28 V (4.7%)2906.2 WDrop/Amp High
500 kcmil253.4 mm²380 A5.47 V (2.28%)234.5 V9.02 V (3.76%)2324.7 WDrop/Amp High
600 kcmil304.0 mm²420 A4.56 V (1.9%)235.4 V7.52 V (3.13%)1937.8 WDrop/Amp High
750 kcmil380.0 mm²475 A3.65 V (1.52%)236.4 V6.02 V (2.51%)1550.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.74 V (1.14%)237.3 V4.51 V (1.88%)1162.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 250 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.65V (1.52%) and delivers 236.4V at the load.

What size aluminum wire is required for 425 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.51V (1.88%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.