⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.72%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.3V (0.9%)
Voltage at Load End476.5 VLoss: 3.47 V (2557.9 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A634.82 V (132.25%)0.0 V1047.15 V (218.16%)467301.5 WDrop/Amp High
12 AWG3.31 mm²20 A398.92 V (83.11%)81.1 V658.03 V (137.09%)293651.7 WDrop/Amp High
10 AWG5.26 mm²30 A251.03 V (52.3%)229.0 V414.08 V (86.27%)184788.4 WDrop/Amp High
8 AWG8.37 mm²50 A157.76 V (32.87%)322.2 V260.22 V (54.21%)116127.5 WDrop/Amp High
6 AWG13.3 mm²65 A99.28 V (20.68%)380.7 V163.76 V (34.12%)73081.7 WDrop/Amp High
4 AWG21.15 mm²85 A62.43 V (13.01%)417.6 V102.98 V (21.45%)45956.8 WDrop/Amp High
3 AWG26.67 mm²100 A49.51 V (10.31%)430.5 V81.67 V (17.01%)36445.0 WDrop/Amp High
2 AWG33.62 mm²115 A39.27 V (8.18%)440.7 V64.78 V (13.5%)28911.0 WDrop/Amp High
1 AWG42.41 mm²130 A31.13 V (6.49%)448.9 V51.36 V (10.7%)22918.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A24.69 V (5.14%)455.3 V40.72 V (8.48%)18171.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.58 V (4.08%)460.4 V32.3 V (6.73%)14414.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.53 V (3.24%)464.5 V25.62 V (5.34%)11433.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.32 V (2.57%)467.7 V20.32 V (4.23%)9067.0 WDrop/Amp High
250 kcmil126.7 mm²255 A10.42 V (2.17%)469.6 V17.19 V (3.58%)7671.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.69 V (1.81%)471.3 V14.33 V (2.99%)6394.7 WDrop/Amp High
350 kcmil177.3 mm²310 A7.45 V (1.55%)472.6 V12.28 V (2.56%)5482.2 WDrop/Amp High
400 kcmil202.7 mm²335 A6.51 V (1.36%)473.5 V10.75 V (2.24%)4795.2 WDrop/Amp High
500 kcmil253.4 mm²380 A5.21 V (1.09%)474.8 V8.6 V (1.79%)3835.8 WDrop/Amp High
600 kcmil304.0 mm²420 A4.34 V (0.9%)475.7 V7.16 V (1.49%)3197.3 WDrop/Amp High
750 kcmil380.0 mm²475 A3.47 V (0.72%)476.5 V5.73 V (1.19%)2557.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.61 V (0.54%)477.4 V4.3 V (0.9%)1918.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 275 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.47V (0.72%) and delivers 476.5V at the load.

What size aluminum wire is required for 425 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.3V (0.9%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.