🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 400 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.22V (6.02%)
Voltage at Load End117.8 VLoss: 2.19 V (930.0 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 400 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1066.21 V (888.51%)0.0 V1758.75 V (1465.63%)453140.9 WDrop/Amp High
12 AWG3.31 mm²20 A670.01 V (558.34%)0.0 V1105.2 V (921.0%)284753.2 WDrop/Amp High
10 AWG5.26 mm²30 A421.62 V (351.35%)0.0 V695.48 V (579.56%)179188.8 WDrop/Amp High
8 AWG8.37 mm²50 A264.96 V (220.8%)0.0 V437.06 V (364.22%)112608.5 WDrop/Amp High
6 AWG13.3 mm²65 A166.75 V (138.96%)0.0 V275.05 V (229.21%)70867.1 WDrop/Amp High
4 AWG21.15 mm²85 A104.86 V (87.38%)15.1 V172.96 V (144.14%)44564.2 WDrop/Amp High
3 AWG26.67 mm²100 A83.15 V (69.3%)36.8 V137.17 V (114.3%)35340.6 WDrop/Amp High
2 AWG33.62 mm²115 A65.96 V (54.97%)54.0 V108.81 V (90.68%)28034.9 WDrop/Amp High
1 AWG42.41 mm²130 A52.29 V (43.58%)67.7 V86.26 V (71.88%)22224.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A41.46 V (34.55%)78.5 V68.39 V (56.99%)17620.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A32.89 V (27.41%)87.1 V54.25 V (45.21%)13977.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A26.09 V (21.74%)93.9 V43.03 V (35.86%)11087.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A20.69 V (17.24%)99.3 V34.13 V (28.44%)8792.3 WDrop/Amp High
250 kcmil126.7 mm²255 A17.5 V (14.59%)102.5 V28.87 V (24.06%)7439.1 WDrop/Amp High
300 kcmil152.0 mm²285 A14.59 V (12.16%)105.4 V24.07 V (20.06%)6200.9 WDrop/Amp High
350 kcmil177.3 mm²310 A12.51 V (10.42%)107.5 V20.63 V (17.19%)5316.0 WDrop/Amp High
400 kcmil202.7 mm²335 A10.94 V (9.12%)109.1 V18.05 V (15.04%)4649.9 WDrop/Amp High
500 kcmil253.4 mm²380 A8.75 V (7.29%)111.2 V14.44 V (12.03%)3719.5 WDrop/Amp High
600 kcmil304.0 mm²420 A7.3 V (6.08%)112.7 V12.03 V (10.03%)3100.4 WDrop/Amp High
750 kcmil380.0 mm²475 A5.84 V (4.86%)114.2 V9.63 V (8.02%)2480.4 W~ ≤5%
1000 kcmil506.7 mm²545 A4.38 V (3.65%)115.6 V7.22 V (6.02%)1860.1 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 400 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 400 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.19V (1.82%) and delivers 117.8V at the load.

What size aluminum wire is required for 425 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.22V (6.02%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.