⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 450 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.37%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.03V (2.93%)
Voltage at Load End234.3 VLoss: 5.69 V (4185.6 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1038.79 V (432.83%)0.0 V1713.52 V (713.97%)764675.2 WDrop/Amp High
12 AWG3.31 mm²20 A652.77 V (271.99%)0.0 V1076.77 V (448.65%)480521.0 WDrop/Amp High
10 AWG5.26 mm²30 A410.78 V (171.16%)0.0 V677.59 V (282.33%)302381.1 WDrop/Amp High
8 AWG8.37 mm²50 A258.15 V (107.56%)0.0 V425.82 V (177.43%)190026.8 WDrop/Amp High
6 AWG13.3 mm²65 A162.46 V (67.69%)77.5 V267.98 V (111.66%)119588.3 WDrop/Amp High
4 AWG21.15 mm²85 A102.16 V (42.57%)137.8 V168.52 V (70.22%)75202.1 WDrop/Amp High
3 AWG26.67 mm²100 A81.02 V (33.76%)159.0 V133.64 V (55.68%)59637.2 WDrop/Amp High
2 AWG33.62 mm²115 A64.27 V (26.78%)175.7 V106.01 V (44.17%)47308.9 WDrop/Amp High
1 AWG42.41 mm²130 A50.95 V (21.23%)189.1 V84.04 V (35.02%)37503.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A40.39 V (16.83%)199.6 V66.63 V (27.76%)29735.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A32.04 V (13.35%)208.0 V52.86 V (22.02%)23587.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A25.42 V (10.59%)214.6 V41.93 V (17.47%)18709.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A20.16 V (8.4%)219.8 V33.25 V (13.85%)14837.0 WDrop/Amp High
250 kcmil126.7 mm²255 A17.05 V (7.11%)222.9 V28.13 V (11.72%)12553.5 WDrop/Amp High
300 kcmil152.0 mm²285 A14.22 V (5.92%)225.8 V23.45 V (9.77%)10464.0 WDrop/Amp High
350 kcmil177.3 mm²310 A12.19 V (5.08%)227.8 V20.1 V (8.38%)8970.8 WDrop/Amp High
400 kcmil202.7 mm²335 A10.66 V (4.44%)229.3 V17.58 V (7.33%)7846.7 WDrop/Amp High
500 kcmil253.4 mm²380 A8.53 V (3.55%)231.5 V14.07 V (5.86%)6276.7 WDrop/Amp High
600 kcmil304.0 mm²420 A7.11 V (2.96%)232.9 V11.72 V (4.89%)5232.0 WDrop/Amp High
750 kcmil380.0 mm²475 A5.69 V (2.37%)234.3 V9.38 V (3.91%)4185.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.26 V (1.78%)235.7 V7.03 V (2.93%)3139.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 450 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 5.69V (2.37%) and delivers 234.3V at the load.

What size aluminum wire is required for 425 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.03V (2.93%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.