🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.74%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.83V (4.51%)
Voltage at Load End233.4 VLoss: 6.57 V (2790.2 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1599.32 V (666.38%)0.0 V2638.13 V (1099.22%)679711.3 WDrop/Amp High
12 AWG3.31 mm²20 A1005.01 V (418.75%)0.0 V1657.8 V (690.75%)427129.8 WDrop/Amp High
10 AWG5.26 mm²30 A632.43 V (263.51%)0.0 V1043.22 V (434.67%)268783.2 WDrop/Amp High
8 AWG8.37 mm²50 A397.44 V (165.6%)0.0 V655.59 V (273.16%)168912.7 WDrop/Amp High
6 AWG13.3 mm²65 A250.12 V (104.22%)0.0 V412.58 V (171.91%)106300.7 WDrop/Amp High
4 AWG21.15 mm²85 A157.29 V (65.54%)82.7 V259.45 V (108.1%)66846.3 WDrop/Amp High
3 AWG26.67 mm²100 A124.73 V (51.97%)115.3 V205.75 V (85.73%)53010.9 WDrop/Amp High
2 AWG33.62 mm²115 A98.95 V (41.23%)141.1 V163.22 V (68.01%)42052.3 WDrop/Amp High
1 AWG42.41 mm²130 A78.44 V (32.68%)161.6 V129.39 V (53.91%)33336.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A62.19 V (25.91%)177.8 V102.59 V (42.74%)26431.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A49.33 V (20.56%)190.7 V81.38 V (33.91%)20966.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A39.13 V (16.3%)200.9 V64.55 V (26.9%)16631.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A31.03 V (12.93%)209.0 V51.19 V (21.33%)13188.4 WDrop/Amp High
250 kcmil126.7 mm²255 A26.26 V (10.94%)213.7 V43.31 V (18.05%)11158.6 WDrop/Amp High
300 kcmil152.0 mm²285 A21.89 V (9.12%)218.1 V36.1 V (15.04%)9301.3 WDrop/Amp High
350 kcmil177.3 mm²310 A18.76 V (7.82%)221.2 V30.95 V (12.9%)7974.1 WDrop/Amp High
400 kcmil202.7 mm²335 A16.41 V (6.84%)223.6 V27.07 V (11.28%)6974.8 WDrop/Amp High
500 kcmil253.4 mm²380 A13.13 V (5.47%)226.9 V21.65 V (9.02%)5579.3 WDrop/Amp High
600 kcmil304.0 mm²420 A10.94 V (4.56%)229.1 V18.05 V (7.52%)4650.7 WDrop/Amp High
750 kcmil380.0 mm²475 A8.75 V (3.65%)231.2 V14.44 V (6.02%)3720.5 W~ ≤5%
1000 kcmil506.7 mm²545 A6.57 V (2.74%)233.4 V10.83 V (4.51%)2790.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 600 feet one-way at 240V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 6.57V (2.74%) and delivers 233.4V at the load.

What size aluminum wire is required for 425 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.83V (4.51%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.