🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.37%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.38V (3.91%)
Voltage at Load End234.3 VLoss: 5.69 V (4185.3 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1385.05 V (577.11%)0.0 V2284.69 V (951.95%)1019567.0 WDrop/Amp High
12 AWG3.31 mm²20 A870.37 V (362.65%)0.0 V1435.7 V (598.21%)640694.7 WDrop/Amp High
10 AWG5.26 mm²30 A547.7 V (228.21%)0.0 V903.45 V (376.44%)403174.8 WDrop/Amp High
8 AWG8.37 mm²50 A344.19 V (143.41%)0.0 V567.76 V (236.57%)253369.1 WDrop/Amp High
6 AWG13.3 mm²65 A216.61 V (90.25%)23.4 V357.3 V (148.88%)159451.1 WDrop/Amp High
4 AWG21.15 mm²85 A136.21 V (56.76%)103.8 V224.69 V (93.62%)100269.5 WDrop/Amp High
3 AWG26.67 mm²100 A108.02 V (45.01%)132.0 V178.18 V (74.24%)79516.3 WDrop/Amp High
2 AWG33.62 mm²115 A85.69 V (35.7%)154.3 V141.35 V (58.9%)63078.5 WDrop/Amp High
1 AWG42.41 mm²130 A67.93 V (28.3%)172.1 V112.05 V (46.69%)50004.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A53.86 V (22.44%)186.1 V88.84 V (37.02%)39646.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A42.72 V (17.8%)197.3 V70.48 V (29.36%)31450.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A33.89 V (14.12%)206.1 V55.9 V (23.29%)24946.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.87 V (11.2%)213.1 V44.33 V (18.47%)19782.6 WDrop/Amp High
250 kcmil126.7 mm²255 A22.74 V (9.47%)217.3 V37.51 V (15.63%)16738.0 WDrop/Amp High
300 kcmil152.0 mm²285 A18.95 V (7.9%)221.0 V31.26 V (13.03%)13952.0 WDrop/Amp High
350 kcmil177.3 mm²310 A16.25 V (6.77%)223.8 V26.8 V (11.17%)11961.1 WDrop/Amp High
400 kcmil202.7 mm²335 A14.21 V (5.92%)225.8 V23.44 V (9.77%)10462.3 WDrop/Amp High
500 kcmil253.4 mm²380 A11.37 V (4.74%)228.6 V18.75 V (7.81%)8369.0 WDrop/Amp High
600 kcmil304.0 mm²420 A9.48 V (3.95%)230.5 V15.63 V (6.51%)6976.0 WDrop/Amp High
750 kcmil380.0 mm²475 A7.58 V (3.16%)232.4 V12.51 V (5.21%)5580.8 W~ ≤5%
1000 kcmil506.7 mm²545 A5.69 V (2.37%)234.3 V9.38 V (3.91%)4185.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 600 feet one-way at 240V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 5.69V (2.37%) and delivers 234.3V at the load.

What size aluminum wire is required for 425 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.38V (3.91%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.