⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 750 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.96%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.72V (4.88%)
Voltage at Load End232.9 VLoss: 7.11 V (5231.6 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1731.32 V (721.38%)0.0 V2855.86 V (1189.94%)1274458.7 WDrop/Amp High
12 AWG3.31 mm²20 A1087.96 V (453.32%)0.0 V1794.62 V (747.76%)800868.3 WDrop/Amp High
10 AWG5.26 mm²30 A684.63 V (285.26%)0.0 V1129.31 V (470.55%)503968.5 WDrop/Amp High
8 AWG8.37 mm²50 A430.24 V (179.27%)0.0 V709.7 V (295.71%)316711.4 WDrop/Amp High
6 AWG13.3 mm²65 A270.76 V (112.82%)0.0 V446.63 V (186.1%)199313.8 WDrop/Amp High
4 AWG21.15 mm²85 A170.27 V (70.94%)69.7 V280.86 V (117.03%)125336.8 WDrop/Amp High
3 AWG26.67 mm²100 A135.03 V (56.26%)105.0 V222.73 V (92.8%)99395.4 WDrop/Amp High
2 AWG33.62 mm²115 A107.11 V (44.63%)132.9 V176.69 V (73.62%)78848.1 WDrop/Amp High
1 AWG42.41 mm²130 A84.91 V (35.38%)155.1 V140.07 V (58.36%)62505.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A67.32 V (28.05%)172.7 V111.05 V (46.27%)49558.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A53.41 V (22.25%)186.6 V88.09 V (36.71%)39313.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A42.36 V (17.65%)197.6 V69.88 V (29.12%)31183.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A33.59 V (14.0%)206.4 V55.41 V (23.09%)24728.3 WDrop/Amp High
250 kcmil126.7 mm²255 A28.42 V (11.84%)211.6 V46.88 V (19.53%)20922.4 WDrop/Amp High
300 kcmil152.0 mm²285 A23.69 V (9.87%)216.3 V39.08 V (16.28%)17440.0 WDrop/Amp High
350 kcmil177.3 mm²310 A20.31 V (8.46%)219.7 V33.5 V (13.96%)14951.3 WDrop/Amp High
400 kcmil202.7 mm²335 A17.77 V (7.4%)222.2 V29.31 V (12.21%)13077.8 WDrop/Amp High
500 kcmil253.4 mm²380 A14.21 V (5.92%)225.8 V23.44 V (9.77%)10461.2 WDrop/Amp High
600 kcmil304.0 mm²420 A11.85 V (4.94%)228.2 V19.54 V (8.14%)8720.0 WDrop/Amp High
750 kcmil380.0 mm²475 A9.48 V (3.95%)230.5 V15.63 V (6.51%)6976.0 W~ ≤5%
1000 kcmil506.7 mm²545 A7.11 V (2.96%)232.9 V11.72 V (4.88%)5231.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 750 feet one-way at 240V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 7.11V (2.96%) and delivers 232.9V at the load.

What size aluminum wire is required for 425 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.72V (4.88%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.