45 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.74%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 3.28V (2.73%)
Voltage at Load End116.7 VLoss: 3.29 V (147.9 W)
Power & Breaker (125%)5.4 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A169.34 V (141.12%)0.0 V279.33 V (232.78%)7620.3 WDrop/Amp High
12 AWG3.31 mm²20 A106.41 V (88.68%)13.6 V175.53 V (146.28%)4788.6 WDrop/Amp High
10 AWG5.26 mm²30 A66.96 V (55.8%)53.0 V110.46 V (92.05%)3013.3 WDrop/Amp High
8 AWG8.37 mm²50 A42.08 V (35.07%)77.9 V69.42 V (57.85%)1893.7 WDrop/Amp High
6 AWG13.3 mm²65 A26.48 V (22.07%)93.5 V43.68 V (36.4%)1191.7 WDrop/Amp High
4 AWG21.15 mm²85 A16.65 V (13.88%)103.3 V27.47 V (22.89%)749.4 WDrop/Amp High
3 AWG26.67 mm²100 A13.21 V (11.01%)106.8 V21.79 V (18.15%)594.3 WDrop/Amp High
2 AWG33.62 mm²115 A10.48 V (8.73%)109.5 V17.28 V (14.4%)471.5 WDrop/Amp High
1 AWG42.41 mm²130 A8.31 V (6.92%)111.7 V13.7 V (11.42%)373.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.58 V (5.49%)113.4 V10.86 V (9.05%)296.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.22 V (4.35%)114.8 V8.62 V (7.18%)235.1 W~ ≤5%
3/0 AWG85.01 mm²200 A4.14 V (3.45%)115.9 V6.83 V (5.7%)186.5 W~ ≤5%
4/0 AWG107.2 mm²230 A3.29 V (2.74%)116.7 V5.42 V (4.52%)147.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.78 V (2.32%)117.2 V4.59 V (3.82%)125.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.32 V (1.93%)117.7 V3.82 V (3.19%)104.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.99 V (1.66%)118.0 V3.28 V (2.73%)89.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.74 V (1.45%)118.3 V2.87 V (2.39%)78.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.39 V (1.16%)118.6 V2.29 V (1.91%)62.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.16 V (0.97%)118.8 V1.91 V (1.59%)52.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.93 V (0.77%)119.1 V1.53 V (1.27%)41.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.7 V (0.58%)119.3 V1.15 V (0.96%)31.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 600 feet one-way at 120V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 3.29V (2.74%) and delivers 116.7V at the load.

What size aluminum wire is required for 45 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 3.28V (2.73%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.