🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 600 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.38%
Aluminum Wire (≤3% Drop)1 AWGDrop: 11.86V (2.47%)
Voltage at Load End468.6 VLoss: 11.44 V (891.5 W)
Power & Breaker (125%)37.41 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 600 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A146.65 V (30.55%)333.3 V241.91 V (50.4%)11430.4 WDrop/Amp High
12 AWG3.31 mm²20 A92.16 V (19.2%)387.8 V152.01 V (31.67%)7182.9 WDrop/Amp High
10 AWG5.26 mm²30 A57.99 V (12.08%)422.0 V95.66 V (19.93%)4520.0 WDrop/Amp High
8 AWG8.37 mm²50 A36.44 V (7.59%)443.6 V60.12 V (12.52%)2840.5 WDrop/Amp High
6 AWG13.3 mm²65 A22.94 V (4.78%)457.1 V37.83 V (7.88%)1787.6 W~ ≤5%
4 AWG21.15 mm²85 A14.42 V (3.0%)465.6 V23.79 V (4.96%)1124.1 W~ ≤5%
3 AWG26.67 mm²100 A11.44 V (2.38%)468.6 V18.87 V (3.93%)891.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A9.07 V (1.89%)470.9 V14.97 V (3.12%)707.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A7.19 V (1.5%)472.8 V11.86 V (2.47%)560.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A5.7 V (1.19%)474.3 V9.41 V (1.96%)444.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.52 V (0.94%)475.5 V7.46 V (1.55%)352.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.59 V (0.75%)476.4 V5.92 V (1.23%)279.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.85 V (0.59%)477.2 V4.69 V (0.98%)221.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.41 V (0.5%)477.6 V3.97 V (0.83%)187.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.01 V (0.42%)478.0 V3.31 V (0.69%)156.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.72 V (0.36%)478.3 V2.84 V (0.59%)134.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.5 V (0.31%)478.5 V2.48 V (0.52%)117.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.2 V (0.25%)478.8 V1.99 V (0.41%)93.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.0 V (0.21%)479.0 V1.66 V (0.34%)78.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.8 V (0.17%)479.2 V1.32 V (0.28%)62.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.6 V (0.13%)479.4 V0.99 V (0.21%)46.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 600 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 600 feet one-way at 480V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 11.44V (2.38%) and delivers 468.6V at the load.

What size aluminum wire is required for 45 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 11.86V (2.47%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.