⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.02%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 16.18V (3.37%)
Voltage at Load End475.1 VLoss: 4.91 V (4672.9 W)
Power & Breaker (125%)457.26 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2389.89 V (497.89%)0.0 V3942.21 V (821.29%)2276680.2 WDrop/Amp High
12 AWG3.31 mm²20 A1501.81 V (312.88%)0.0 V2477.28 V (516.1%)1430663.1 WDrop/Amp High
10 AWG5.26 mm²30 A945.05 V (196.89%)0.0 V1558.9 V (324.77%)900284.2 WDrop/Amp High
8 AWG8.37 mm²50 A593.9 V (123.73%)0.0 V979.66 V (204.1%)565770.0 WDrop/Amp High
6 AWG13.3 mm²65 A373.76 V (77.87%)106.2 V616.53 V (128.44%)356052.2 WDrop/Amp High
4 AWG21.15 mm²85 A235.03 V (48.97%)245.0 V387.7 V (80.77%)223900.5 WDrop/Amp High
3 AWG26.67 mm²100 A186.39 V (38.83%)293.6 V307.45 V (64.05%)177558.9 WDrop/Amp High
2 AWG33.62 mm²115 A147.86 V (30.8%)332.1 V243.9 V (50.81%)140853.5 WDrop/Amp High
1 AWG42.41 mm²130 A117.21 V (24.42%)362.8 V193.35 V (40.28%)111659.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A92.93 V (19.36%)387.1 V153.3 V (31.94%)88530.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A73.72 V (15.36%)406.3 V121.6 V (25.33%)70228.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A58.48 V (12.18%)421.5 V96.46 V (20.1%)55705.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A46.37 V (9.66%)433.6 V76.49 V (15.94%)44174.4 WDrop/Amp High
250 kcmil126.7 mm²255 A39.23 V (8.17%)440.8 V64.72 V (13.48%)37375.6 WDrop/Amp High
300 kcmil152.0 mm²285 A32.7 V (6.81%)447.3 V53.95 V (11.24%)31154.6 WDrop/Amp High
350 kcmil177.3 mm²310 A28.04 V (5.84%)452.0 V46.25 V (9.64%)26708.9 WDrop/Amp High
400 kcmil202.7 mm²335 A24.52 V (5.11%)455.5 V40.45 V (8.43%)23362.1 WDrop/Amp High
500 kcmil253.4 mm²380 A19.62 V (4.09%)460.4 V32.36 V (6.74%)18687.8 WDrop/Amp High
600 kcmil304.0 mm²420 A16.35 V (3.41%)463.6 V26.97 V (5.62%)15577.3 WDrop/Amp High
750 kcmil380.0 mm²475 A13.08 V (2.73%)466.9 V21.58 V (4.5%)12461.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.81 V (2.04%)470.2 V16.18 V (3.37%)9345.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 800 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.91V (1.02%) and delivers 475.1V at the load.

What size aluminum wire is required for 550 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 16.18V (3.37%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.