600 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.89%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.01V (2.92%)
Voltage at Load End237.9 VLoss: 2.12 V (1274.4 W)
Power & Breaker (125%)144.0 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1034.85 V (431.19%)0.0 V1707.03 V (711.26%)620912.8 WDrop/Amp High
12 AWG3.31 mm²20 A650.3 V (270.96%)0.0 V1072.69 V (446.96%)390180.8 WDrop/Amp High
10 AWG5.26 mm²30 A409.22 V (170.51%)0.0 V675.02 V (281.26%)245532.0 WDrop/Amp High
8 AWG8.37 mm²50 A257.17 V (107.15%)0.0 V424.21 V (176.75%)154300.9 WDrop/Amp High
6 AWG13.3 mm²65 A161.84 V (67.43%)78.2 V266.96 V (111.23%)97105.2 WDrop/Amp High
4 AWG21.15 mm²85 A101.77 V (42.41%)138.2 V167.88 V (69.95%)61063.8 WDrop/Amp High
3 AWG26.67 mm²100 A80.71 V (33.63%)159.3 V133.13 V (55.47%)48425.1 WDrop/Amp High
2 AWG33.62 mm²115 A64.02 V (26.68%)176.0 V105.61 V (44.0%)38414.6 WDrop/Amp High
1 AWG42.41 mm²130 A50.75 V (21.15%)189.2 V83.72 V (34.88%)30452.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A40.24 V (16.77%)199.8 V66.38 V (27.66%)24144.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A31.92 V (13.3%)208.1 V52.66 V (21.94%)19153.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A25.32 V (10.55%)214.7 V41.77 V (17.4%)15192.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A20.08 V (8.37%)219.9 V33.12 V (13.8%)12047.6 WDrop/Amp High
250 kcmil126.7 mm²255 A16.99 V (7.08%)223.0 V28.02 V (11.68%)10193.4 WDrop/Amp High
300 kcmil152.0 mm²285 A14.16 V (5.9%)225.8 V23.36 V (9.73%)8496.7 WDrop/Amp High
350 kcmil177.3 mm²310 A12.14 V (5.06%)227.9 V20.03 V (8.34%)7284.3 WDrop/Amp High
400 kcmil202.7 mm²335 A10.62 V (4.42%)229.4 V17.52 V (7.3%)6371.5 WDrop/Amp High
500 kcmil253.4 mm²380 A8.49 V (3.54%)231.5 V14.01 V (5.84%)5096.7 WDrop/Amp High
600 kcmil304.0 mm²420 A7.08 V (2.95%)232.9 V11.68 V (4.87%)4248.4 WDrop/Amp High
750 kcmil380.0 mm²475 A5.66 V (2.36%)234.3 V9.34 V (3.89%)3398.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.25 V (1.77%)235.8 V7.01 V (2.92%)2548.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 275 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.12V (0.89%) and delivers 237.9V at the load.

What size aluminum wire is required for 600 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.01V (2.92%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.