⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.34%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.38V (1.12%)
Voltage at Load End478.4 VLoss: 1.63 V (1835.6 W)
Power & Breaker (125%)540.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A794.37 V (165.49%)0.0 V1310.34 V (272.99%)894326.1 WDrop/Amp High
12 AWG3.31 mm²20 A499.18 V (104.0%)0.0 V823.41 V (171.54%)561993.4 WDrop/Amp High
10 AWG5.26 mm²30 A314.12 V (65.44%)165.9 V518.16 V (107.95%)353649.8 WDrop/Amp High
8 AWG8.37 mm²50 A197.41 V (41.13%)282.6 V325.63 V (67.84%)222245.9 WDrop/Amp High
6 AWG13.3 mm²65 A124.23 V (25.88%)355.8 V204.92 V (42.69%)139864.5 WDrop/Amp High
4 AWG21.15 mm²85 A78.12 V (16.28%)401.9 V128.87 V (26.85%)87952.6 WDrop/Amp High
3 AWG26.67 mm²100 A61.95 V (12.91%)418.0 V102.19 V (21.29%)69748.7 WDrop/Amp High
2 AWG33.62 mm²115 A49.15 V (10.24%)430.9 V81.07 V (16.89%)55330.1 WDrop/Amp High
1 AWG42.41 mm²130 A38.96 V (8.12%)441.0 V64.27 V (13.39%)43862.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A30.89 V (6.44%)449.1 V50.95 V (10.62%)34776.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A24.5 V (5.1%)455.5 V40.42 V (8.42%)27587.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.44 V (4.05%)460.6 V32.06 V (6.68%)21882.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.41 V (3.21%)464.6 V25.42 V (5.3%)17352.6 WDrop/Amp High
250 kcmil126.7 mm²255 A13.04 V (2.72%)467.0 V21.51 V (4.48%)14681.9 WDrop/Amp High
300 kcmil152.0 mm²285 A10.87 V (2.26%)469.1 V17.93 V (3.74%)12238.1 WDrop/Amp High
350 kcmil177.3 mm²310 A9.32 V (1.94%)470.7 V15.37 V (3.2%)10491.8 WDrop/Amp High
400 kcmil202.7 mm²335 A8.15 V (1.7%)471.8 V13.45 V (2.8%)9177.1 WDrop/Amp High
500 kcmil253.4 mm²380 A6.52 V (1.36%)473.5 V10.76 V (2.24%)7341.0 WDrop/Amp High
600 kcmil304.0 mm²420 A5.44 V (1.13%)474.6 V8.97 V (1.87%)6119.1 WDrop/Amp High
750 kcmil380.0 mm²475 A4.35 V (0.91%)475.7 V7.17 V (1.49%)4895.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.26 V (0.68%)476.7 V5.38 V (1.12%)3671.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 225 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.63V (0.34%) and delivers 478.4V at the load.

What size aluminum wire is required for 650 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.38V (1.12%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.