🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.38%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.98V (1.25%)
Voltage at Load End478.2 VLoss: 1.81 V (2039.5 W)
Power & Breaker (125%)540.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A882.63 V (183.88%)0.0 V1455.93 V (303.32%)993695.6 WDrop/Amp High
12 AWG3.31 mm²20 A554.64 V (115.55%)0.0 V914.9 V (190.61%)624437.1 WDrop/Amp High
10 AWG5.26 mm²30 A349.03 V (72.71%)131.0 V575.73 V (119.94%)392944.3 WDrop/Amp High
8 AWG8.37 mm²50 A219.34 V (45.7%)260.7 V361.81 V (75.38%)246939.9 WDrop/Amp High
6 AWG13.3 mm²65 A138.04 V (28.76%)342.0 V227.69 V (47.44%)155405.0 WDrop/Amp High
4 AWG21.15 mm²85 A86.8 V (18.08%)393.2 V143.18 V (29.83%)97725.1 WDrop/Amp High
3 AWG26.67 mm²100 A68.84 V (14.34%)411.2 V113.55 V (23.66%)77498.6 WDrop/Amp High
2 AWG33.62 mm²115 A54.61 V (11.38%)425.4 V90.08 V (18.77%)61477.9 WDrop/Amp High
1 AWG42.41 mm²130 A43.29 V (9.02%)436.7 V71.41 V (14.88%)48735.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A34.32 V (7.15%)445.7 V56.61 V (11.79%)38640.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A27.23 V (5.67%)452.8 V44.91 V (9.36%)30652.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A21.6 V (4.5%)458.4 V35.62 V (7.42%)24313.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.13 V (3.57%)462.9 V28.25 V (5.89%)19280.7 WDrop/Amp High
250 kcmil126.7 mm²255 A14.49 V (3.02%)465.5 V23.9 V (4.98%)16313.2 WDrop/Amp High
300 kcmil152.0 mm²285 A12.08 V (2.52%)467.9 V19.92 V (4.15%)13597.9 WDrop/Amp High
350 kcmil177.3 mm²310 A10.35 V (2.16%)469.6 V17.08 V (3.56%)11657.6 WDrop/Amp High
400 kcmil202.7 mm²335 A9.06 V (1.89%)470.9 V14.94 V (3.11%)10196.8 WDrop/Amp High
500 kcmil253.4 mm²380 A7.24 V (1.51%)472.8 V11.95 V (2.49%)8156.6 WDrop/Amp High
600 kcmil304.0 mm²420 A6.04 V (1.26%)474.0 V9.96 V (2.08%)6799.0 WDrop/Amp High
750 kcmil380.0 mm²475 A4.83 V (1.01%)475.2 V7.97 V (1.66%)5439.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.62 V (0.75%)476.4 V5.98 V (1.25%)4079.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 250 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.81V (0.38%) and delivers 478.2V at the load.

What size aluminum wire is required for 650 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.98V (1.25%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.