⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.83%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.57V (2.74%)
Voltage at Load End238.0 VLoss: 2.0 V (2243.5 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A970.89 V (404.54%)0.0 V1601.52 V (667.3%)1093065.2 WDrop/Amp High
12 AWG3.31 mm²20 A610.11 V (254.21%)0.0 V1006.39 V (419.33%)686880.8 WDrop/Amp High
10 AWG5.26 mm²30 A383.93 V (159.97%)0.0 V633.3 V (263.88%)432238.7 WDrop/Amp High
8 AWG8.37 mm²50 A241.27 V (100.53%)0.0 V397.99 V (165.83%)271633.9 WDrop/Amp High
6 AWG13.3 mm²65 A151.84 V (63.27%)88.2 V250.46 V (104.36%)170945.5 WDrop/Amp High
4 AWG21.15 mm²85 A95.48 V (39.78%)144.5 V157.5 V (65.63%)107497.7 WDrop/Amp High
3 AWG26.67 mm²100 A75.72 V (31.55%)164.3 V124.9 V (52.04%)85248.4 WDrop/Amp High
2 AWG33.62 mm²115 A60.07 V (25.03%)179.9 V99.08 V (41.28%)67625.7 WDrop/Amp High
1 AWG42.41 mm²130 A47.62 V (19.84%)192.4 V78.55 V (32.73%)53609.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A37.75 V (15.73%)202.2 V62.28 V (25.95%)42504.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A29.95 V (12.48%)210.1 V49.4 V (20.58%)33717.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.76 V (9.9%)216.2 V39.19 V (16.33%)26744.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.84 V (7.85%)221.2 V31.07 V (12.95%)21208.7 WDrop/Amp High
250 kcmil126.7 mm²255 A15.94 V (6.64%)224.1 V26.29 V (10.95%)17944.6 WDrop/Amp High
300 kcmil152.0 mm²285 A13.29 V (5.54%)226.7 V21.92 V (9.13%)14957.7 WDrop/Amp High
350 kcmil177.3 mm²310 A11.39 V (4.75%)228.6 V18.79 V (7.83%)12823.3 WDrop/Amp High
400 kcmil202.7 mm²335 A9.96 V (4.15%)230.0 V16.43 V (6.85%)11216.5 WDrop/Amp High
500 kcmil253.4 mm²380 A7.97 V (3.32%)232.0 V13.15 V (5.48%)8972.3 WDrop/Amp High
600 kcmil304.0 mm²420 A6.64 V (2.77%)233.4 V10.96 V (4.57%)7478.9 WDrop/Amp High
750 kcmil380.0 mm²475 A5.31 V (2.21%)234.7 V8.77 V (3.65%)5983.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.99 V (1.66%)236.0 V6.57 V (2.74%)4487.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 275 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.0V (0.83%) and delivers 238.0V at the load.

What size aluminum wire is required for 650 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.57V (2.74%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.