🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.03%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.18V (3.41%)
Voltage at Load End237.5 VLoss: 2.48 V (1734.7 W)
Power & Breaker (125%)168.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1207.33 V (503.05%)0.0 V1991.53 V (829.8%)845131.3 WDrop/Amp High
12 AWG3.31 mm²20 A758.68 V (316.12%)0.0 V1251.48 V (521.45%)531079.5 WDrop/Amp High
10 AWG5.26 mm²30 A477.42 V (198.93%)0.0 V787.53 V (328.14%)334196.4 WDrop/Amp High
8 AWG8.37 mm²50 A300.03 V (125.01%)0.0 V494.91 V (206.21%)210020.7 WDrop/Amp High
6 AWG13.3 mm²65 A188.82 V (78.67%)51.2 V311.46 V (129.77%)132170.9 WDrop/Amp High
4 AWG21.15 mm²85 A118.74 V (49.47%)121.3 V195.86 V (81.61%)83114.6 WDrop/Amp High
3 AWG26.67 mm²100 A94.16 V (39.23%)145.8 V155.32 V (64.72%)65912.0 WDrop/Amp High
2 AWG33.62 mm²115 A74.7 V (31.12%)165.3 V123.21 V (51.34%)52286.5 WDrop/Amp High
1 AWG42.41 mm²130 A59.21 V (24.67%)180.8 V97.67 V (40.7%)41449.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A46.95 V (19.56%)193.1 V77.44 V (32.27%)32863.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A37.24 V (15.52%)202.8 V61.43 V (25.6%)26069.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.54 V (12.31%)210.5 V48.73 V (20.3%)20678.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.43 V (9.76%)216.6 V38.64 V (16.1%)16398.1 WDrop/Amp High
250 kcmil126.7 mm²255 A19.82 V (8.26%)220.2 V32.69 V (13.62%)13874.3 WDrop/Amp High
300 kcmil152.0 mm²285 A16.52 V (6.88%)223.5 V27.25 V (11.36%)11565.0 WDrop/Amp High
350 kcmil177.3 mm²310 A14.16 V (5.9%)225.8 V23.36 V (9.73%)9914.7 WDrop/Amp High
400 kcmil202.7 mm²335 A12.39 V (5.16%)227.6 V20.44 V (8.52%)8672.3 WDrop/Amp High
500 kcmil253.4 mm²380 A9.91 V (4.13%)230.1 V16.35 V (6.81%)6937.1 WDrop/Amp High
600 kcmil304.0 mm²420 A8.26 V (3.44%)231.7 V13.63 V (5.68%)5782.5 WDrop/Amp High
750 kcmil380.0 mm²475 A6.61 V (2.75%)233.4 V10.9 V (4.54%)4626.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.96 V (2.07%)235.0 V8.18 V (3.41%)3469.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 275 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.48V (1.03%) and delivers 237.5V at the load.

What size aluminum wire is required for 700 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.18V (3.41%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.