🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.3%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 20.6V (4.29%)
Voltage at Load End473.8 VLoss: 6.25 V (7569.3 W)
Power & Breaker (125%)581.97 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3041.68 V (633.68%)0.0 V5017.36 V (1045.28%)3687845.5 WDrop/Amp High
12 AWG3.31 mm²20 A1911.39 V (398.21%)0.0 V3152.9 V (656.85%)2317437.7 WDrop/Amp High
10 AWG5.26 mm²30 A1202.8 V (250.58%)0.0 V1984.05 V (413.34%)1458311.5 WDrop/Amp High
8 AWG8.37 mm²50 A755.88 V (157.47%)0.0 V1246.85 V (259.76%)916453.8 WDrop/Amp High
6 AWG13.3 mm²65 A475.69 V (99.1%)4.3 V784.67 V (163.47%)576745.8 WDrop/Amp High
4 AWG21.15 mm²85 A299.13 V (62.32%)180.9 V493.43 V (102.8%)362681.7 WDrop/Amp High
3 AWG26.67 mm²100 A237.22 V (49.42%)242.8 V391.3 V (81.52%)287616.0 WDrop/Amp High
2 AWG33.62 mm²115 A188.18 V (39.2%)291.8 V310.41 V (64.67%)228159.4 WDrop/Amp High
1 AWG42.41 mm²130 A149.18 V (31.08%)330.8 V246.08 V (51.27%)180870.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A118.28 V (24.64%)361.7 V195.1 V (40.65%)143404.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A93.83 V (19.55%)386.2 V154.77 V (32.24%)113758.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A74.42 V (15.5%)405.6 V122.76 V (25.58%)90233.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A59.02 V (12.3%)421.0 V97.35 V (20.28%)71555.2 WDrop/Amp High
250 kcmil126.7 mm²255 A49.93 V (10.4%)430.1 V82.37 V (17.16%)60542.4 WDrop/Amp High
300 kcmil152.0 mm²285 A41.62 V (8.67%)438.4 V68.66 V (14.3%)50465.3 WDrop/Amp High
350 kcmil177.3 mm²310 A35.68 V (7.43%)444.3 V58.86 V (12.26%)43264.1 WDrop/Amp High
400 kcmil202.7 mm²335 A31.21 V (6.5%)448.8 V51.49 V (10.73%)37842.7 WDrop/Amp High
500 kcmil253.4 mm²380 A24.97 V (5.2%)455.0 V41.18 V (8.58%)30271.2 WDrop/Amp High
600 kcmil304.0 mm²420 A20.81 V (4.34%)459.2 V34.33 V (7.15%)25232.6 WDrop/Amp High
750 kcmil380.0 mm²475 A16.65 V (3.47%)463.4 V27.46 V (5.72%)20186.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.49 V (2.6%)467.5 V20.6 V (4.29%)15138.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 800 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.25V (1.3%) and delivers 473.8V at the load.

What size aluminum wire is required for 700 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 20.6V (4.29%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.