🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.18%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.34V (3.89%)
Voltage at Load End237.2 VLoss: 2.83 V (2265.7 W)
Power & Breaker (125%)192.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1379.81 V (574.92%)0.0 V2276.04 V (948.35%)1103844.9 WDrop/Amp High
12 AWG3.31 mm²20 A867.07 V (361.28%)0.0 V1430.26 V (595.94%)693654.8 WDrop/Amp High
10 AWG5.26 mm²30 A545.63 V (227.34%)0.0 V900.03 V (375.01%)436501.4 WDrop/Amp High
8 AWG8.37 mm²50 A342.89 V (142.87%)0.0 V565.61 V (235.67%)274312.7 WDrop/Amp High
6 AWG13.3 mm²65 A215.79 V (89.91%)24.2 V355.95 V (148.31%)172631.4 WDrop/Amp High
4 AWG21.15 mm²85 A135.7 V (56.54%)104.3 V223.84 V (93.27%)108557.8 WDrop/Amp High
3 AWG26.67 mm²100 A107.61 V (44.84%)132.4 V177.51 V (73.96%)86089.1 WDrop/Amp High
2 AWG33.62 mm²115 A85.37 V (35.57%)154.6 V140.81 V (58.67%)68292.6 WDrop/Amp High
1 AWG42.41 mm²130 A67.67 V (28.2%)172.3 V111.63 V (46.51%)54138.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A53.65 V (22.36%)186.3 V88.51 V (36.88%)42923.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A42.56 V (17.73%)197.4 V70.21 V (29.25%)34050.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A33.76 V (14.07%)206.2 V55.69 V (23.2%)27008.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.77 V (11.16%)213.2 V44.16 V (18.4%)21417.9 WDrop/Amp High
250 kcmil126.7 mm²255 A22.65 V (9.44%)217.3 V37.37 V (15.57%)18121.5 WDrop/Amp High
300 kcmil152.0 mm²285 A18.88 V (7.87%)221.1 V31.15 V (12.98%)15105.2 WDrop/Amp High
350 kcmil177.3 mm²310 A16.19 V (6.74%)223.8 V26.7 V (11.13%)12949.8 WDrop/Amp High
400 kcmil202.7 mm²335 A14.16 V (5.9%)225.8 V23.36 V (9.73%)11327.1 WDrop/Amp High
500 kcmil253.4 mm²380 A11.33 V (4.72%)228.7 V18.68 V (7.78%)9060.8 WDrop/Amp High
600 kcmil304.0 mm²420 A9.44 V (3.93%)230.6 V15.57 V (6.49%)7552.6 WDrop/Amp High
750 kcmil380.0 mm²475 A7.55 V (3.15%)232.4 V12.46 V (5.19%)6042.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.66 V (2.36%)234.3 V9.34 V (3.89%)4531.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 275 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.83V (1.18%) and delivers 237.2V at the load.

What size aluminum wire is required for 800 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.34V (3.89%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.