🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.49%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 23.54V (4.9%)
Voltage at Load End472.9 VLoss: 7.13 V (9886.4 W)
Power & Breaker (125%)665.11 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3476.21 V (724.21%)0.0 V5734.12 V (1194.61%)4816777.8 WDrop/Amp High
12 AWG3.31 mm²20 A2184.45 V (455.09%)0.0 V3603.32 V (750.69%)3026857.4 WDrop/Amp High
10 AWG5.26 mm²30 A1374.62 V (286.38%)0.0 V2267.49 V (472.39%)1904733.4 WDrop/Amp High
8 AWG8.37 mm²50 A863.86 V (179.97%)0.0 V1424.97 V (296.87%)1197000.9 WDrop/Amp High
6 AWG13.3 mm²65 A543.65 V (113.26%)0.0 V896.76 V (186.83%)753300.6 WDrop/Amp High
4 AWG21.15 mm²85 A341.87 V (71.22%)138.1 V563.92 V (117.48%)473706.8 WDrop/Amp High
3 AWG26.67 mm²100 A271.11 V (56.48%)208.9 V447.21 V (93.17%)375661.7 WDrop/Amp High
2 AWG33.62 mm²115 A215.07 V (44.81%)264.9 V354.76 V (73.91%)298004.1 WDrop/Amp High
1 AWG42.41 mm²130 A170.49 V (35.52%)309.5 V281.23 V (58.59%)236239.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A135.18 V (28.16%)344.8 V222.98 V (46.45%)187304.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A107.23 V (22.34%)372.8 V176.88 V (36.85%)148582.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A85.05 V (17.72%)394.9 V140.3 V (29.23%)117855.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A67.45 V (14.05%)412.6 V111.26 V (23.18%)93459.9 WDrop/Amp High
250 kcmil126.7 mm²255 A57.07 V (11.89%)422.9 V94.14 V (19.61%)79075.8 WDrop/Amp High
300 kcmil152.0 mm²285 A47.57 V (9.91%)432.4 V78.47 V (16.35%)65913.8 WDrop/Amp High
350 kcmil177.3 mm²310 A40.78 V (8.5%)439.2 V67.27 V (14.01%)56508.2 WDrop/Amp High
400 kcmil202.7 mm²335 A35.67 V (7.43%)444.3 V58.84 V (12.26%)49427.2 WDrop/Amp High
500 kcmil253.4 mm²380 A28.53 V (5.94%)451.5 V47.07 V (9.81%)39537.9 WDrop/Amp High
600 kcmil304.0 mm²420 A23.78 V (4.96%)456.2 V39.23 V (8.17%)32956.9 WDrop/Amp High
750 kcmil380.0 mm²475 A19.03 V (3.96%)461.0 V31.39 V (6.54%)26365.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A14.27 V (2.97%)465.7 V23.54 V (4.9%)19772.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 800 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 7.13V (1.49%) and delivers 472.9V at the load.

What size aluminum wire is required for 800 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 23.54V (4.9%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.