🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 200 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 6.08V (2.92%)
Voltage at Load End202.1 VLoss: 5.86 V (1116.6 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 200 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A119.49 V (57.45%)88.5 V197.11 V (94.76%)22766.8 WDrop/Amp High
12 AWG3.31 mm²20 A75.09 V (36.1%)132.9 V123.86 V (59.55%)14306.6 WDrop/Amp High
10 AWG5.26 mm²30 A47.25 V (22.72%)160.7 V77.94 V (37.47%)9002.8 WDrop/Amp High
8 AWG8.37 mm²50 A29.7 V (14.28%)178.3 V48.98 V (23.55%)5657.7 WDrop/Amp High
6 AWG13.3 mm²65 A18.69 V (8.98%)189.3 V30.83 V (14.82%)3560.5 WDrop/Amp High
4 AWG21.15 mm²85 A11.75 V (5.65%)196.2 V19.38 V (9.32%)2239.0 WDrop/Amp High
3 AWG26.67 mm²100 A9.32 V (4.48%)198.7 V15.37 V (7.39%)1775.6 WDrop/Amp High
2 AWG33.62 mm²115 A7.39 V (3.55%)200.6 V12.19 V (5.86%)1408.5 W~ ≤5%
1 AWG42.41 mm²130 A5.86 V (2.82%)202.1 V9.67 V (4.65%)1116.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.65 V (2.23%)203.4 V7.66 V (3.68%)885.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.69 V (1.77%)204.3 V6.08 V (2.92%)702.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.92 V (1.41%)205.1 V4.82 V (2.32%)557.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.32 V (1.11%)205.7 V3.82 V (1.84%)441.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.96 V (0.94%)206.0 V3.24 V (1.56%)373.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.64 V (0.79%)206.4 V2.7 V (1.3%)311.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.4 V (0.67%)206.6 V2.31 V (1.11%)267.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.23 V (0.59%)206.8 V2.02 V (0.97%)233.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.98 V (0.47%)207.0 V1.62 V (0.78%)186.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.82 V (0.39%)207.2 V1.35 V (0.65%)155.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.65 V (0.31%)207.3 V1.08 V (0.52%)124.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.49 V (0.24%)207.5 V0.81 V (0.39%)93.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 200 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 200 feet one-way at 208V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 5.86V (2.82%) and delivers 202.1V at the load.

What size aluminum wire is required for 110 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 6.08V (2.92%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.