🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.66%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 6.63V (2.76%)
Voltage at Load End233.6 VLoss: 6.39 V (1217.3 W)
Power & Breaker (125%)45.73 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A164.31 V (68.46%)75.7 V271.03 V (112.93%)31304.4 WDrop/Amp High
12 AWG3.31 mm²20 A103.25 V (43.02%)136.8 V170.31 V (70.96%)19671.6 WDrop/Amp High
10 AWG5.26 mm²30 A64.97 V (27.07%)175.0 V107.17 V (44.66%)12378.9 WDrop/Amp High
8 AWG8.37 mm²50 A40.83 V (17.01%)199.2 V67.35 V (28.06%)7779.3 WDrop/Amp High
6 AWG13.3 mm²65 A25.7 V (10.71%)214.3 V42.39 V (17.66%)4895.7 WDrop/Amp High
4 AWG21.15 mm²85 A16.16 V (6.73%)223.8 V26.65 V (11.11%)3078.6 WDrop/Amp High
3 AWG26.67 mm²100 A12.81 V (5.34%)227.2 V21.14 V (8.81%)2441.4 WDrop/Amp High
2 AWG33.62 mm²115 A10.17 V (4.24%)229.8 V16.77 V (6.99%)1936.7 W~ ≤5%
1 AWG42.41 mm²130 A8.06 V (3.36%)231.9 V13.29 V (5.54%)1535.3 W~ ≤5%
1/0 AWG53.49 mm²150 A6.39 V (2.66%)233.6 V10.54 V (4.39%)1217.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A5.07 V (2.11%)234.9 V8.36 V (3.48%)965.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.02 V (1.68%)236.0 V6.63 V (2.76%)765.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.19 V (1.33%)236.8 V5.26 V (2.19%)607.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.7 V (1.12%)237.3 V4.45 V (1.85%)513.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.25 V (0.94%)237.8 V3.71 V (1.55%)428.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.93 V (0.8%)238.1 V3.18 V (1.32%)367.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.69 V (0.7%)238.3 V2.78 V (1.16%)321.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.35 V (0.56%)238.7 V2.22 V (0.93%)257.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.12 V (0.47%)238.9 V1.85 V (0.77%)214.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.9 V (0.37%)239.1 V1.48 V (0.62%)171.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.67 V (0.28%)239.3 V1.11 V (0.46%)128.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 275 feet one-way at 240V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 6.39V (2.66%) and delivers 233.6V at the load.

What size aluminum wire is required for 110 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 6.63V (2.76%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.