🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 300 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.66%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 5.74V (2.76%)
Voltage at Load End202.5 VLoss: 5.53 V (1053.4 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 300 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A179.24 V (86.17%)28.8 V295.67 V (142.15%)34150.2 WDrop/Amp High
12 AWG3.31 mm²20 A112.64 V (54.15%)95.4 V185.8 V (89.32%)21459.9 WDrop/Amp High
10 AWG5.26 mm²30 A70.88 V (34.08%)137.1 V116.92 V (56.21%)13504.3 WDrop/Amp High
8 AWG8.37 mm²50 A44.54 V (21.41%)163.5 V73.47 V (35.32%)8486.5 WDrop/Amp High
6 AWG13.3 mm²65 A28.03 V (13.48%)180.0 V46.24 V (22.23%)5340.8 WDrop/Amp High
4 AWG21.15 mm²85 A17.63 V (8.47%)190.4 V29.08 V (13.98%)3358.5 WDrop/Amp High
3 AWG26.67 mm²100 A13.98 V (6.72%)194.0 V23.06 V (11.09%)2663.4 WDrop/Amp High
2 AWG33.62 mm²115 A11.09 V (5.33%)196.9 V18.29 V (8.79%)2112.8 WDrop/Amp High
1 AWG42.41 mm²130 A8.79 V (4.23%)199.2 V14.5 V (6.97%)1674.9 W~ ≤5%
1/0 AWG53.49 mm²150 A6.97 V (3.35%)201.0 V11.5 V (5.53%)1328.0 W~ ≤5%
2/0 AWG67.43 mm²175 A5.53 V (2.66%)202.5 V9.12 V (4.38%)1053.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.39 V (2.11%)203.6 V7.23 V (3.48%)835.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.48 V (1.67%)204.5 V5.74 V (2.76%)662.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.94 V (1.41%)205.1 V4.85 V (2.33%)560.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.45 V (1.18%)205.5 V4.05 V (1.95%)467.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.1 V (1.01%)205.9 V3.47 V (1.67%)400.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.84 V (0.88%)206.2 V3.03 V (1.46%)350.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.47 V (0.71%)206.5 V2.43 V (1.17%)280.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.23 V (0.59%)206.8 V2.02 V (0.97%)233.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.98 V (0.47%)207.0 V1.62 V (0.78%)186.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.74 V (0.35%)207.3 V1.21 V (0.58%)140.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 300 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 300 feet one-way at 208V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 5.53V (2.66%) and delivers 202.5V at the load.

What size aluminum wire is required for 110 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 5.74V (2.76%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.