110 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 350 ft (106.7 m) one-way run.
Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.46%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 5.66V (2.72%)
Voltage at Load End202.9 VLoss: 5.12 V (974.8 W)
Power & Breaker (125%)39.63 kW150A Breaker Recommended
All AWG & kcmil Wire Gauges for 110 Amps at 350 Feet (208V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 209.12 V (100.54%) | 0.0 V | 344.94 V (165.84%) | 39841.9 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 131.41 V (63.18%) | 76.6 V | 216.76 V (104.21%) | 25036.6 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 82.69 V (39.76%) | 125.3 V | 136.4 V (65.58%) | 15755.0 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 51.97 V (24.98%) | 156.0 V | 85.72 V (41.21%) | 9901.0 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 32.7 V (15.72%) | 175.3 V | 53.95 V (25.94%) | 6230.9 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 20.57 V (9.89%) | 187.4 V | 33.92 V (16.31%) | 3918.3 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 16.31 V (7.84%) | 191.7 V | 26.9 V (12.93%) | 3107.3 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 12.94 V (6.22%) | 195.1 V | 21.34 V (10.26%) | 2464.9 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 10.26 V (4.93%) | 197.7 V | 16.92 V (8.13%) | 1954.0 W | ~ ≤5% |
| 1/0 AWG | 53.49 mm² | 150 A | 8.13 V (3.91%) | 199.9 V | 13.41 V (6.45%) | 1549.3 W | ~ ≤5% |
| 2/0 AWG | 67.43 mm² | 175 A | 6.45 V (3.1%) | 201.5 V | 10.64 V (5.12%) | 1229.0 W | ~ ≤5% |
| 3/0 AWG | 85.01 mm² | 200 A | 5.12 V (2.46%) | 202.9 V | 8.44 V (4.06%) | 974.8 W | ✓ PASS (≤3%) |
| 4/0 AWG | 107.2 mm² | 230 A | 4.06 V (1.95%) | 203.9 V | 6.69 V (3.22%) | 773.1 W | ✓ PASS (≤3%) |
| 250 kcmil | 126.7 mm² | 255 A | 3.43 V (1.65%) | 204.6 V | 5.66 V (2.72%) | 654.1 W | ✓ PASS (≤3%) |
| 300 kcmil | 152.0 mm² | 285 A | 2.86 V (1.38%) | 205.1 V | 4.72 V (2.27%) | 545.2 W | ✓ PASS (≤3%) |
| 350 kcmil | 177.3 mm² | 310 A | 2.45 V (1.18%) | 205.5 V | 4.05 V (1.95%) | 467.4 W | ✓ PASS (≤3%) |
| 400 kcmil | 202.7 mm² | 335 A | 2.15 V (1.03%) | 205.9 V | 3.54 V (1.7%) | 408.8 W | ✓ PASS (≤3%) |
| 500 kcmil | 253.4 mm² | 380 A | 1.72 V (0.83%) | 206.3 V | 2.83 V (1.36%) | 327.0 W | ✓ PASS (≤3%) |
| 600 kcmil | 304.0 mm² | 420 A | 1.43 V (0.69%) | 206.6 V | 2.36 V (1.13%) | 272.6 W | ✓ PASS (≤3%) |
| 750 kcmil | 380.0 mm² | 475 A | 1.14 V (0.55%) | 206.9 V | 1.89 V (0.91%) | 218.1 W | ✓ PASS (≤3%) |
| 1000 kcmil | 506.7 mm² | 545 A | 0.86 V (0.41%) | 207.1 V | 1.42 V (0.68%) | 163.6 W | ✓ PASS (≤3%) |
Frequently Asked Engineering Questions
What size copper wire do I need for 110 amps at 350 feet (208V)?
To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 350 feet one-way at 208V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 5.12V (2.46%) and delivers 202.9V at the load.
What size aluminum wire is required for 110 amps at 350 feet?
Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 5.66V (2.72%).
What breaker size is needed for a 110A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.
Compare Other Distances & Amperages
110 Amp Wire Size by Distance (208V)
110A at 20 ft (208V)110A at 30 ft (208V)110A at 40 ft (208V)110A at 50 ft (208V)110A at 60 ft (208V)110A at 75 ft (208V)110A at 80 ft (208V)110A at 100 ft (208V)110A at 120 ft (208V)110A at 125 ft (208V)110A at 150 ft (208V)110A at 175 ft (208V)