🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 13.24V (2.76%)
Voltage at Load End466.6 VLoss: 13.38 V (5213.9 W)
Power & Breaker (125%)187.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A977.68 V (203.68%)0.0 V1612.72 V (335.98%)381014.7 WDrop/Amp High
12 AWG3.31 mm²20 A614.38 V (127.99%)0.0 V1013.43 V (211.13%)239429.1 WDrop/Amp High
10 AWG5.26 mm²30 A386.61 V (80.54%)93.4 V637.73 V (132.86%)150667.4 WDrop/Amp High
8 AWG8.37 mm²50 A242.96 V (50.62%)237.0 V400.77 V (83.49%)94684.6 WDrop/Amp High
6 AWG13.3 mm²65 A152.9 V (31.85%)327.1 V252.22 V (52.54%)59587.3 WDrop/Amp High
4 AWG21.15 mm²85 A96.15 V (20.03%)383.8 V158.6 V (33.04%)37470.9 WDrop/Amp High
3 AWG26.67 mm²100 A76.25 V (15.89%)403.8 V125.78 V (26.2%)29715.4 WDrop/Amp High
2 AWG33.62 mm²115 A60.49 V (12.6%)419.5 V99.78 V (20.79%)23572.6 WDrop/Amp High
1 AWG42.41 mm²130 A47.95 V (9.99%)432.0 V79.1 V (16.48%)18686.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A38.02 V (7.92%)442.0 V62.71 V (13.06%)14816.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A30.16 V (6.28%)449.8 V49.75 V (10.36%)11753.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.92 V (4.98%)456.1 V39.46 V (8.22%)9322.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.97 V (3.95%)461.0 V31.29 V (6.52%)7392.8 W~ ≤5%
250 kcmil126.7 mm²255 A16.05 V (3.34%)463.9 V26.48 V (5.52%)6255.0 W~ ≤5%
300 kcmil152.0 mm²285 A13.38 V (2.79%)466.6 V22.07 V (4.6%)5213.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A11.47 V (2.39%)468.5 V18.92 V (3.94%)4469.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A10.03 V (2.09%)470.0 V16.55 V (3.45%)3909.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A8.03 V (1.67%)472.0 V13.24 V (2.76%)3127.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A6.69 V (1.39%)473.3 V11.03 V (2.3%)2606.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A5.35 V (1.11%)474.6 V8.83 V (1.84%)2085.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.01 V (0.84%)476.0 V6.62 V (1.38%)1564.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 800 feet one-way at 480V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 13.38V (2.79%) and delivers 466.6V at the load.

What size aluminum wire is required for 225 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 13.24V (2.76%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.