325 Amp Wire Size at 400 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 6.38V (2.66%)
Voltage at Load End234.2 VLoss: 5.8 V (3262.6 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 400 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A706.11 V (294.21%)0.0 V1164.74 V (485.31%)397478.2 WDrop/Amp High
12 AWG3.31 mm²20 A443.72 V (184.88%)0.0 V731.92 V (304.97%)249774.9 WDrop/Amp High
10 AWG5.26 mm²30 A279.22 V (116.34%)0.0 V460.58 V (191.91%)157177.7 WDrop/Amp High
8 AWG8.37 mm²50 A175.47 V (73.11%)64.5 V289.45 V (120.6%)98776.0 WDrop/Amp High
6 AWG13.3 mm²65 A110.43 V (46.01%)129.6 V182.16 V (75.9%)62162.0 WDrop/Amp High
4 AWG21.15 mm²85 A69.44 V (28.93%)170.6 V114.55 V (47.73%)39090.1 WDrop/Amp High
3 AWG26.67 mm²100 A55.07 V (22.95%)184.9 V90.84 V (37.85%)30999.4 WDrop/Amp High
2 AWG33.62 mm²115 A43.69 V (18.2%)196.3 V72.06 V (30.03%)24591.2 WDrop/Amp High
1 AWG42.41 mm²130 A34.63 V (14.43%)205.4 V57.12 V (23.8%)19494.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A27.46 V (11.44%)212.5 V45.29 V (18.87%)15456.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A21.78 V (9.08%)218.2 V35.93 V (14.97%)12260.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.28 V (7.2%)222.7 V28.5 V (11.87%)9725.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.7 V (5.71%)226.3 V22.6 V (9.42%)7712.3 WDrop/Amp High
250 kcmil126.7 mm²255 A11.59 V (4.83%)228.4 V19.12 V (7.97%)6525.3 WDrop/Amp High
300 kcmil152.0 mm²285 A9.66 V (4.03%)230.3 V15.94 V (6.64%)5439.2 WDrop/Amp High
350 kcmil177.3 mm²310 A8.28 V (3.45%)231.7 V13.66 V (5.69%)4663.0 WDrop/Amp High
400 kcmil202.7 mm²335 A7.25 V (3.02%)232.8 V11.95 V (4.98%)4078.7 W~ ≤5%
500 kcmil253.4 mm²380 A5.8 V (2.41%)234.2 V9.56 V (3.98%)3262.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.83 V (2.01%)235.2 V7.97 V (3.32%)2719.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.86 V (1.61%)236.1 V6.38 V (2.66%)2175.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.9 V (1.21%)237.1 V4.78 V (1.99%)1631.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 400 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 400 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 5.8V (2.41%) and delivers 234.2V at the load.

What size aluminum wire is required for 325 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 6.38V (2.66%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.