⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 500 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.91%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.9V (2.88%)
Voltage at Load End233.0 VLoss: 6.97 V (2266.3 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1019.17 V (424.66%)0.0 V1681.16 V (700.48%)331231.9 WDrop/Amp High
12 AWG3.31 mm²20 A640.45 V (266.85%)0.0 V1056.44 V (440.18%)208145.7 WDrop/Amp High
10 AWG5.26 mm²30 A403.02 V (167.92%)0.0 V664.79 V (277.0%)130981.4 WDrop/Amp High
8 AWG8.37 mm²50 A253.27 V (105.53%)0.0 V417.78 V (174.07%)82313.3 WDrop/Amp High
6 AWG13.3 mm²65 A159.39 V (66.41%)80.6 V262.92 V (109.55%)51801.7 WDrop/Amp High
4 AWG21.15 mm²85 A100.23 V (41.76%)139.8 V165.33 V (68.89%)32575.0 WDrop/Amp High
3 AWG26.67 mm²100 A79.49 V (33.12%)160.5 V131.11 V (54.63%)25832.9 WDrop/Amp High
2 AWG33.62 mm²115 A63.05 V (26.27%)176.9 V104.01 V (43.34%)20492.6 WDrop/Amp High
1 AWG42.41 mm²130 A49.99 V (20.83%)190.0 V82.45 V (34.36%)16245.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A39.63 V (16.51%)200.4 V65.37 V (27.24%)12880.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A31.44 V (13.1%)208.6 V51.86 V (21.61%)10217.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A24.94 V (10.39%)215.1 V41.13 V (17.14%)8104.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A19.78 V (8.24%)220.2 V32.62 V (13.59%)6426.9 WDrop/Amp High
250 kcmil126.7 mm²255 A16.73 V (6.97%)223.3 V27.6 V (11.5%)5437.7 WDrop/Amp High
300 kcmil152.0 mm²285 A13.95 V (5.81%)226.1 V23.01 V (9.59%)4532.6 WDrop/Amp High
350 kcmil177.3 mm²310 A11.96 V (4.98%)228.0 V19.72 V (8.22%)3885.9 WDrop/Amp High
400 kcmil202.7 mm²335 A10.46 V (4.36%)229.5 V17.25 V (7.19%)3398.9 W~ ≤5%
500 kcmil253.4 mm²380 A8.37 V (3.49%)231.6 V13.8 V (5.75%)2718.9 W~ ≤5%
600 kcmil304.0 mm²420 A6.97 V (2.91%)233.0 V11.5 V (4.79%)2266.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A5.58 V (2.32%)234.4 V9.2 V (3.83%)1813.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.18 V (1.74%)235.8 V6.9 V (2.88%)1359.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 500 feet one-way at 240V (1-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 6.97V (2.91%) and delivers 233.0V at the load.

What size aluminum wire is required for 325 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.9V (2.88%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.