⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 800 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.0%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.19V (9.91%)
Voltage at Load End11.8 VLoss: 0.24 V (8.4 W)
Power & Breaker (125%)0.42 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 800 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A175.61 V (1463.43%)0.0 V289.68 V (2413.98%)6146.4 WDrop/Amp High
12 AWG3.31 mm²20 A110.35 V (919.62%)0.0 V182.03 V (1516.94%)3862.4 WDrop/Amp High
10 AWG5.26 mm²30 A69.44 V (578.7%)0.0 V114.55 V (954.58%)2430.5 WDrop/Amp High
8 AWG8.37 mm²50 A43.64 V (363.67%)0.0 V71.99 V (599.89%)1527.4 WDrop/Amp High
6 AWG13.3 mm²65 A27.46 V (228.87%)0.0 V45.3 V (377.52%)961.2 WDrop/Amp High
4 AWG21.15 mm²85 A17.27 V (143.92%)0.0 V28.49 V (237.4%)604.5 WDrop/Amp High
3 AWG26.67 mm²100 A13.7 V (114.13%)0.0 V22.59 V (188.27%)479.4 WDrop/Amp High
2 AWG33.62 mm²115 A10.86 V (90.54%)1.1 V17.92 V (149.35%)380.3 WDrop/Amp High
1 AWG42.41 mm²130 A8.61 V (71.77%)3.4 V14.21 V (118.39%)301.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.83 V (56.91%)5.2 V11.26 V (93.87%)239.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.42 V (45.14%)6.6 V8.94 V (74.46%)189.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.3 V (35.81%)7.7 V7.09 V (59.06%)150.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.41 V (28.39%)8.6 V5.62 V (46.84%)119.3 WDrop/Amp High
250 kcmil126.7 mm²255 A2.88 V (24.02%)9.1 V4.76 V (39.63%)100.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.4 V (20.03%)9.6 V3.96 V (33.03%)84.1 WDrop/Amp High
350 kcmil177.3 mm²310 A2.06 V (17.17%)9.9 V3.4 V (28.32%)72.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.8 V (15.02%)10.2 V2.97 V (24.77%)63.1 WDrop/Amp High
500 kcmil253.4 mm²380 A1.44 V (12.01%)10.6 V2.38 V (19.81%)50.5 WDrop/Amp High
600 kcmil304.0 mm²420 A1.2 V (10.01%)10.8 V1.98 V (16.52%)42.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.96 V (8.01%)11.0 V1.59 V (13.21%)33.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.72 V (6.01%)11.3 V1.19 V (9.91%)25.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 800 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 800 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.24V (2.0%) and delivers 11.8V at the load.

What size aluminum wire is required for 35 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.19V (9.91%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.