🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.21%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 5.84V (2.43%)
Voltage at Load End234.7 VLoss: 5.31 V (1990.9 W)
Power & Breaker (125%)90.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A646.78 V (269.49%)0.0 V1066.89 V (444.54%)242544.1 WDrop/Amp High
12 AWG3.31 mm²20 A406.44 V (169.35%)0.0 V670.43 V (279.35%)152414.4 WDrop/Amp High
10 AWG5.26 mm²30 A255.76 V (106.57%)0.0 V421.89 V (175.79%)95911.0 WDrop/Amp High
8 AWG8.37 mm²50 A160.73 V (66.97%)79.3 V265.13 V (110.47%)60273.8 WDrop/Amp High
6 AWG13.3 mm²65 A101.15 V (42.15%)138.8 V166.85 V (69.52%)37931.7 WDrop/Amp High
4 AWG21.15 mm²85 A63.61 V (26.5%)176.4 V104.92 V (43.72%)23853.0 WDrop/Amp High
3 AWG26.67 mm²100 A50.44 V (21.02%)189.6 V83.21 V (34.67%)18916.1 WDrop/Amp High
2 AWG33.62 mm²115 A40.02 V (16.67%)200.0 V66.01 V (27.5%)15005.7 WDrop/Amp High
1 AWG42.41 mm²130 A31.72 V (13.22%)208.3 V52.33 V (21.8%)11895.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.15 V (10.48%)214.8 V41.49 V (17.29%)9431.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.95 V (8.31%)220.0 V32.91 V (13.71%)7481.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.83 V (6.59%)224.2 V26.1 V (10.88%)5934.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.55 V (5.23%)227.5 V20.7 V (8.63%)4706.1 WDrop/Amp High
250 kcmil126.7 mm²255 A10.62 V (4.42%)229.4 V17.51 V (7.3%)3981.8 WDrop/Amp High
300 kcmil152.0 mm²285 A8.85 V (3.69%)231.1 V14.6 V (6.08%)3319.0 WDrop/Amp High
350 kcmil177.3 mm²310 A7.59 V (3.16%)232.4 V12.52 V (5.22%)2845.4 WDrop/Amp High
400 kcmil202.7 mm²335 A6.64 V (2.77%)233.4 V10.95 V (4.56%)2488.9 WDrop/Amp High
500 kcmil253.4 mm²380 A5.31 V (2.21%)234.7 V8.76 V (3.65%)1990.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.43 V (1.84%)235.6 V7.3 V (3.04%)1659.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.54 V (1.48%)236.5 V5.84 V (2.43%)1327.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.66 V (1.11%)237.3 V4.38 V (1.82%)995.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 275 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 5.31V (2.21%) and delivers 234.7V at the load.

What size aluminum wire is required for 375 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 5.84V (2.43%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.