🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 200 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.21%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.13V (1.5%)
Voltage at Load End205.5 VLoss: 2.53 V (1860.3 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 200 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A461.68 V (221.96%)0.0 V761.56 V (366.14%)339855.7 WDrop/Amp High
12 AWG3.31 mm²20 A290.12 V (139.48%)0.0 V478.57 V (230.08%)213564.9 WDrop/Amp High
10 AWG5.26 mm²30 A182.57 V (87.77%)25.4 V301.15 V (144.78%)134391.6 WDrop/Amp High
8 AWG8.37 mm²50 A114.73 V (55.16%)93.3 V189.25 V (90.99%)84456.4 WDrop/Amp High
6 AWG13.3 mm²65 A72.2 V (34.71%)135.8 V119.1 V (57.26%)53150.4 WDrop/Amp High
4 AWG21.15 mm²85 A45.4 V (21.83%)162.6 V74.9 V (36.01%)33423.2 WDrop/Amp High
3 AWG26.67 mm²100 A36.01 V (17.31%)172.0 V59.39 V (28.56%)26505.4 WDrop/Amp High
2 AWG33.62 mm²115 A28.56 V (13.73%)179.4 V47.12 V (22.65%)21026.2 WDrop/Amp High
1 AWG42.41 mm²130 A22.64 V (10.89%)185.4 V37.35 V (17.96%)16668.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.95 V (8.63%)190.0 V29.61 V (14.24%)13215.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.24 V (6.85%)193.8 V23.49 V (11.29%)10483.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.3 V (5.43%)196.7 V18.63 V (8.96%)8315.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.96 V (4.31%)199.0 V14.78 V (7.1%)6594.2 WDrop/Amp High
250 kcmil126.7 mm²255 A7.58 V (3.64%)200.4 V12.5 V (6.01%)5579.3 WDrop/Amp High
300 kcmil152.0 mm²285 A6.32 V (3.04%)201.7 V10.42 V (5.01%)4650.7 WDrop/Amp High
350 kcmil177.3 mm²310 A5.42 V (2.6%)202.6 V8.93 V (4.3%)3987.0 WDrop/Amp High
400 kcmil202.7 mm²335 A4.74 V (2.28%)203.3 V7.81 V (3.76%)3487.4 WDrop/Amp High
500 kcmil253.4 mm²380 A3.79 V (1.82%)204.2 V6.25 V (3.01%)2789.7 WDrop/Amp High
600 kcmil304.0 mm²420 A3.16 V (1.52%)204.8 V5.21 V (2.51%)2325.3 WDrop/Amp High
750 kcmil380.0 mm²475 A2.53 V (1.21%)205.5 V4.17 V (2.0%)1860.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.9 V (0.91%)206.1 V3.13 V (1.5%)1395.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 200 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 200 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.53V (1.21%) and delivers 205.5V at the load.

What size aluminum wire is required for 425 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.13V (1.5%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.