425 Amp Wire Size at 300 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.69V (2.25%)
Voltage at Load End204.2 VLoss: 3.79 V (2790.4 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 300 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A692.53 V (332.95%)0.0 V1142.34 V (549.2%)509783.5 WDrop/Amp High
12 AWG3.31 mm²20 A435.18 V (209.22%)0.0 V717.85 V (345.12%)320347.3 WDrop/Amp High
10 AWG5.26 mm²30 A273.85 V (131.66%)0.0 V451.73 V (217.18%)201587.4 WDrop/Amp High
8 AWG8.37 mm²50 A172.1 V (82.74%)35.9 V283.88 V (136.48%)126684.5 WDrop/Amp High
6 AWG13.3 mm²65 A108.3 V (52.07%)99.7 V178.65 V (85.89%)79725.5 WDrop/Amp High
4 AWG21.15 mm²85 A68.11 V (32.74%)139.9 V112.34 V (54.01%)50134.7 WDrop/Amp High
3 AWG26.67 mm²100 A54.01 V (25.97%)154.0 V89.09 V (42.83%)39758.1 WDrop/Amp High
2 AWG33.62 mm²115 A42.85 V (20.6%)165.2 V70.67 V (33.98%)31539.3 WDrop/Amp High
1 AWG42.41 mm²130 A33.96 V (16.33%)174.0 V56.03 V (26.94%)25002.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A26.93 V (12.95%)181.1 V44.42 V (21.36%)19823.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A21.36 V (10.27%)186.6 V35.24 V (16.94%)15725.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.94 V (8.15%)191.1 V27.95 V (13.44%)12473.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.44 V (6.46%)194.6 V22.16 V (10.66%)9891.3 WDrop/Amp High
250 kcmil126.7 mm²255 A11.37 V (5.47%)196.6 V18.75 V (9.02%)8369.0 WDrop/Amp High
300 kcmil152.0 mm²285 A9.48 V (4.56%)198.5 V15.63 V (7.52%)6976.0 WDrop/Amp High
350 kcmil177.3 mm²310 A8.12 V (3.91%)199.9 V13.4 V (6.44%)5980.5 WDrop/Amp High
400 kcmil202.7 mm²335 A7.11 V (3.42%)200.9 V11.72 V (5.64%)5231.1 WDrop/Amp High
500 kcmil253.4 mm²380 A5.68 V (2.73%)202.3 V9.38 V (4.51%)4184.5 WDrop/Amp High
600 kcmil304.0 mm²420 A4.74 V (2.28%)203.3 V7.82 V (3.76%)3488.0 WDrop/Amp High
750 kcmil380.0 mm²475 A3.79 V (1.82%)204.2 V6.25 V (3.01%)2790.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.84 V (1.37%)205.2 V4.69 V (2.25%)2092.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 300 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 300 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.79V (1.82%) and delivers 204.2V at the load.

What size aluminum wire is required for 425 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.69V (2.25%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.