🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.13%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.47V (2.63%)
Voltage at Load End203.6 VLoss: 4.42 V (3255.5 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A807.95 V (388.44%)0.0 V1332.74 V (640.74%)594747.4 WDrop/Amp High
12 AWG3.31 mm²20 A507.71 V (244.09%)0.0 V837.49 V (402.64%)373738.6 WDrop/Amp High
10 AWG5.26 mm²30 A319.49 V (153.6%)0.0 V527.01 V (253.37%)235185.3 WDrop/Amp High
8 AWG8.37 mm²50 A200.78 V (96.53%)7.2 V331.19 V (159.23%)147798.6 WDrop/Amp High
6 AWG13.3 mm²65 A126.36 V (60.75%)81.6 V208.43 V (100.21%)93013.1 WDrop/Amp High
4 AWG21.15 mm²85 A79.46 V (38.2%)128.5 V131.07 V (63.01%)58490.5 WDrop/Amp High
3 AWG26.67 mm²100 A63.01 V (30.29%)145.0 V103.94 V (49.97%)46384.5 WDrop/Amp High
2 AWG33.62 mm²115 A49.99 V (24.03%)158.0 V82.45 V (39.64%)36795.8 WDrop/Amp High
1 AWG42.41 mm²130 A39.63 V (19.05%)168.4 V65.36 V (31.43%)29169.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.42 V (15.1%)176.6 V51.82 V (24.92%)23127.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A24.92 V (11.98%)183.1 V41.11 V (19.76%)18346.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.77 V (9.5%)188.2 V32.61 V (15.68%)14552.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.68 V (7.54%)192.3 V25.86 V (12.43%)11539.9 WDrop/Amp High
250 kcmil126.7 mm²255 A13.26 V (6.38%)194.7 V21.88 V (10.52%)9763.8 WDrop/Amp High
300 kcmil152.0 mm²285 A11.06 V (5.32%)196.9 V18.24 V (8.77%)8138.6 WDrop/Amp High
350 kcmil177.3 mm²310 A9.48 V (4.56%)198.5 V15.64 V (7.52%)6977.3 WDrop/Amp High
400 kcmil202.7 mm²335 A8.29 V (3.99%)199.7 V13.68 V (6.57%)6103.0 WDrop/Amp High
500 kcmil253.4 mm²380 A6.63 V (3.19%)201.4 V10.94 V (5.26%)4881.9 WDrop/Amp High
600 kcmil304.0 mm²420 A5.53 V (2.66%)202.5 V9.12 V (4.38%)4069.3 WDrop/Amp High
750 kcmil380.0 mm²475 A4.42 V (2.13%)203.6 V7.29 V (3.51%)3255.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.32 V (1.59%)204.7 V5.47 V (2.63%)2441.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 350 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 4.42V (2.13%) and delivers 203.6V at the load.

What size aluminum wire is required for 425 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.47V (2.63%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.