🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 350 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.13%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.32V (2.63%)
Voltage at Load End234.9 VLoss: 5.11 V (2170.3 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A932.94 V (388.72%)0.0 V1538.91 V (641.21%)396498.3 WDrop/Amp High
12 AWG3.31 mm²20 A586.26 V (244.27%)0.0 V967.05 V (402.94%)249159.0 WDrop/Amp High
10 AWG5.26 mm²30 A368.92 V (153.72%)0.0 V608.54 V (253.56%)156790.2 WDrop/Amp High
8 AWG8.37 mm²50 A231.84 V (96.6%)8.2 V382.43 V (159.35%)98532.4 WDrop/Amp High
6 AWG13.3 mm²65 A145.9 V (60.79%)94.1 V240.67 V (100.28%)62008.8 WDrop/Amp High
4 AWG21.15 mm²85 A91.75 V (38.23%)148.3 V151.34 V (63.06%)38993.7 WDrop/Amp High
3 AWG26.67 mm²100 A72.76 V (30.32%)167.2 V120.02 V (50.01%)30923.0 WDrop/Amp High
2 AWG33.62 mm²115 A57.72 V (24.05%)182.3 V95.21 V (39.67%)24530.5 WDrop/Amp High
1 AWG42.41 mm²130 A45.76 V (19.06%)194.2 V75.48 V (31.45%)19446.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A36.28 V (15.12%)203.7 V59.84 V (24.93%)15418.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A28.78 V (11.99%)211.2 V47.47 V (19.78%)12230.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A22.83 V (9.51%)217.2 V37.65 V (15.69%)9701.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.1 V (7.54%)221.9 V29.86 V (12.44%)7693.3 WDrop/Amp High
250 kcmil126.7 mm²255 A15.32 V (6.38%)224.7 V25.26 V (10.53%)6509.2 WDrop/Amp High
300 kcmil152.0 mm²285 A12.77 V (5.32%)227.2 V21.06 V (8.77%)5425.8 WDrop/Amp High
350 kcmil177.3 mm²310 A10.94 V (4.56%)229.1 V18.05 V (7.52%)4651.5 WDrop/Amp High
400 kcmil202.7 mm²335 A9.57 V (3.99%)230.4 V15.79 V (6.58%)4068.7 WDrop/Amp High
500 kcmil253.4 mm²380 A7.66 V (3.19%)232.3 V12.63 V (5.26%)3254.6 WDrop/Amp High
600 kcmil304.0 mm²420 A6.38 V (2.66%)233.6 V10.53 V (4.39%)2712.9 WDrop/Amp High
750 kcmil380.0 mm²475 A5.11 V (2.13%)234.9 V8.42 V (3.51%)2170.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.83 V (1.6%)236.2 V6.32 V (2.63%)1627.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 350 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 5.11V (2.13%) and delivers 234.9V at the load.

What size aluminum wire is required for 425 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.32V (2.63%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.