⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 400 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.11%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.25V (2.61%)
Voltage at Load End234.9 VLoss: 5.05 V (3720.5 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 400 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A923.37 V (384.74%)0.0 V1523.13 V (634.64%)679711.3 WDrop/Amp High
12 AWG3.31 mm²20 A580.24 V (241.77%)0.0 V957.13 V (398.8%)427129.8 WDrop/Amp High
10 AWG5.26 mm²30 A365.13 V (152.14%)0.0 V602.3 V (250.96%)268783.2 WDrop/Amp High
8 AWG8.37 mm²50 A229.46 V (95.61%)10.5 V378.51 V (157.71%)168912.7 WDrop/Amp High
6 AWG13.3 mm²65 A144.41 V (60.17%)95.6 V238.2 V (99.25%)106300.7 WDrop/Amp High
4 AWG21.15 mm²85 A90.81 V (37.84%)149.2 V149.79 V (62.41%)66846.3 WDrop/Amp High
3 AWG26.67 mm²100 A72.01 V (30.01%)168.0 V118.79 V (49.5%)53010.9 WDrop/Amp High
2 AWG33.62 mm²115 A57.13 V (23.8%)182.9 V94.23 V (39.26%)42052.3 WDrop/Amp High
1 AWG42.41 mm²130 A45.29 V (18.87%)194.7 V74.7 V (31.13%)33336.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A35.91 V (14.96%)204.1 V59.23 V (24.68%)26431.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A28.48 V (11.87%)211.5 V46.98 V (19.58%)20966.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A22.59 V (9.41%)217.4 V37.27 V (15.53%)16631.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.92 V (7.47%)222.1 V29.55 V (12.31%)13188.4 WDrop/Amp High
250 kcmil126.7 mm²255 A15.16 V (6.32%)224.8 V25.0 V (10.42%)11158.6 WDrop/Amp High
300 kcmil152.0 mm²285 A12.64 V (5.26%)227.4 V20.84 V (8.68%)9301.3 WDrop/Amp High
350 kcmil177.3 mm²310 A10.83 V (4.51%)229.2 V17.87 V (7.45%)7974.1 WDrop/Amp High
400 kcmil202.7 mm²335 A9.48 V (3.95%)230.5 V15.63 V (6.51%)6974.8 WDrop/Amp High
500 kcmil253.4 mm²380 A7.58 V (3.16%)232.4 V12.5 V (5.21%)5579.3 WDrop/Amp High
600 kcmil304.0 mm²420 A6.32 V (2.63%)233.7 V10.42 V (4.34%)4650.7 WDrop/Amp High
750 kcmil380.0 mm²475 A5.05 V (2.11%)234.9 V8.34 V (3.47%)3720.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.79 V (1.58%)236.2 V6.25 V (2.61%)2790.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 400 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 400 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 5.05V (2.11%) and delivers 234.9V at the load.

What size aluminum wire is required for 425 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.25V (2.61%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.