🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 450 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.05%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.12V (6.77%)
Voltage at Load End117.5 VLoss: 2.46 V (1046.3 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 450 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1199.49 V (999.58%)0.0 V1978.6 V (1648.83%)509783.5 WDrop/Amp High
12 AWG3.31 mm²20 A753.76 V (628.13%)0.0 V1243.35 V (1036.12%)320347.3 WDrop/Amp High
10 AWG5.26 mm²30 A474.32 V (395.27%)0.0 V782.41 V (652.01%)201587.4 WDrop/Amp High
8 AWG8.37 mm²50 A298.08 V (248.4%)0.0 V491.69 V (409.75%)126684.5 WDrop/Amp High
6 AWG13.3 mm²65 A187.59 V (156.32%)0.0 V309.44 V (257.86%)79725.5 WDrop/Amp High
4 AWG21.15 mm²85 A117.96 V (98.3%)2.0 V194.59 V (162.15%)50134.7 WDrop/Amp High
3 AWG26.67 mm²100 A93.55 V (77.96%)26.5 V154.31 V (128.59%)39758.1 WDrop/Amp High
2 AWG33.62 mm²115 A74.21 V (61.84%)45.8 V122.41 V (102.01%)31539.3 WDrop/Amp High
1 AWG42.41 mm²130 A58.83 V (49.02%)61.2 V97.04 V (80.87%)25002.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A46.64 V (38.87%)73.4 V76.94 V (64.12%)19823.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A37.0 V (30.83%)83.0 V61.03 V (50.86%)15725.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.35 V (24.46%)90.7 V48.41 V (40.34%)12473.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.27 V (19.39%)96.7 V38.39 V (31.99%)9891.3 WDrop/Amp High
250 kcmil126.7 mm²255 A19.69 V (16.41%)100.3 V32.48 V (27.07%)8369.0 WDrop/Amp High
300 kcmil152.0 mm²285 A16.41 V (13.68%)103.6 V27.08 V (22.56%)6976.0 WDrop/Amp High
350 kcmil177.3 mm²310 A14.07 V (11.73%)105.9 V23.21 V (19.34%)5980.5 WDrop/Amp High
400 kcmil202.7 mm²335 A12.31 V (10.26%)107.7 V20.3 V (16.92%)5231.1 WDrop/Amp High
500 kcmil253.4 mm²380 A9.85 V (8.2%)110.2 V16.24 V (13.53%)4184.5 WDrop/Amp High
600 kcmil304.0 mm²420 A8.21 V (6.84%)111.8 V13.54 V (11.28%)3488.0 WDrop/Amp High
750 kcmil380.0 mm²475 A6.57 V (5.47%)113.4 V10.83 V (9.03%)2790.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.92 V (4.1%)115.1 V8.12 V (6.77%)2092.7 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 450 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 450 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.46V (2.05%) and delivers 117.5V at the load.

What size aluminum wire is required for 425 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.12V (6.77%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.