🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 500 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.02V (7.52%)
Voltage at Load End117.3 VLoss: 2.73 V (1162.6 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 500 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1332.77 V (1110.64%)0.0 V2198.44 V (1832.04%)566426.1 WDrop/Amp High
12 AWG3.31 mm²20 A837.51 V (697.92%)0.0 V1381.5 V (1151.25%)355941.5 WDrop/Amp High
10 AWG5.26 mm²30 A527.03 V (439.19%)0.0 V869.35 V (724.46%)223986.0 WDrop/Amp High
8 AWG8.37 mm²50 A331.2 V (276.0%)0.0 V546.33 V (455.27%)140760.6 WDrop/Amp High
6 AWG13.3 mm²65 A208.43 V (173.69%)0.0 V343.82 V (286.51%)88583.9 WDrop/Amp High
4 AWG21.15 mm²85 A131.07 V (109.23%)0.0 V216.21 V (180.17%)55705.3 WDrop/Amp High
3 AWG26.67 mm²100 A103.94 V (86.62%)16.1 V171.46 V (142.88%)44175.7 WDrop/Amp High
2 AWG33.62 mm²115 A82.46 V (68.71%)37.5 V136.01 V (113.34%)35043.6 WDrop/Amp High
1 AWG42.41 mm²130 A65.37 V (54.47%)54.6 V107.82 V (89.85%)27780.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A51.83 V (43.19%)68.2 V85.49 V (71.24%)22025.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A41.11 V (34.26%)78.9 V67.81 V (56.51%)17472.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A32.61 V (27.17%)87.4 V53.79 V (44.83%)13859.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A25.86 V (21.55%)94.1 V42.66 V (35.55%)10990.4 WDrop/Amp High
250 kcmil126.7 mm²255 A21.88 V (18.23%)98.1 V36.09 V (30.08%)9298.9 WDrop/Amp High
300 kcmil152.0 mm²285 A18.24 V (15.2%)101.8 V30.08 V (25.07%)7751.1 WDrop/Amp High
350 kcmil177.3 mm²310 A15.64 V (13.03%)104.4 V25.79 V (21.49%)6645.0 WDrop/Amp High
400 kcmil202.7 mm²335 A13.68 V (11.4%)106.3 V22.56 V (18.8%)5812.4 WDrop/Amp High
500 kcmil253.4 mm²380 A10.94 V (9.12%)109.1 V18.05 V (15.04%)4649.4 WDrop/Amp High
600 kcmil304.0 mm²420 A9.12 V (7.6%)110.9 V15.04 V (12.53%)3875.5 WDrop/Amp High
750 kcmil380.0 mm²475 A7.3 V (6.08%)112.7 V12.03 V (10.03%)3100.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.47 V (4.56%)114.5 V9.02 V (7.52%)2325.2 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 500 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 500 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.73V (2.28%) and delivers 117.3V at the load.

What size aluminum wire is required for 425 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.02V (7.52%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.