⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 500 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.02V (3.76%)
Voltage at Load End234.5 VLoss: 5.47 V (2325.2 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1332.77 V (555.32%)0.0 V2198.44 V (916.02%)566426.1 WDrop/Amp High
12 AWG3.31 mm²20 A837.51 V (348.96%)0.0 V1381.5 V (575.62%)355941.5 WDrop/Amp High
10 AWG5.26 mm²30 A527.03 V (219.59%)0.0 V869.35 V (362.23%)223986.0 WDrop/Amp High
8 AWG8.37 mm²50 A331.2 V (138.0%)0.0 V546.33 V (227.64%)140760.6 WDrop/Amp High
6 AWG13.3 mm²65 A208.43 V (86.85%)31.6 V343.82 V (143.26%)88583.9 WDrop/Amp High
4 AWG21.15 mm²85 A131.07 V (54.61%)108.9 V216.21 V (90.09%)55705.3 WDrop/Amp High
3 AWG26.67 mm²100 A103.94 V (43.31%)136.1 V171.46 V (71.44%)44175.7 WDrop/Amp High
2 AWG33.62 mm²115 A82.46 V (34.36%)157.5 V136.01 V (56.67%)35043.6 WDrop/Amp High
1 AWG42.41 mm²130 A65.37 V (27.24%)174.6 V107.82 V (44.93%)27780.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A51.83 V (21.59%)188.2 V85.49 V (35.62%)22025.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A41.11 V (17.13%)198.9 V67.81 V (28.26%)17472.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A32.61 V (13.59%)207.4 V53.79 V (22.41%)13859.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A25.86 V (10.77%)214.1 V42.66 V (17.77%)10990.4 WDrop/Amp High
250 kcmil126.7 mm²255 A21.88 V (9.12%)218.1 V36.09 V (15.04%)9298.9 WDrop/Amp High
300 kcmil152.0 mm²285 A18.24 V (7.6%)221.8 V30.08 V (12.53%)7751.1 WDrop/Amp High
350 kcmil177.3 mm²310 A15.64 V (6.51%)224.4 V25.79 V (10.75%)6645.0 WDrop/Amp High
400 kcmil202.7 mm²335 A13.68 V (5.7%)226.3 V22.56 V (9.4%)5812.4 WDrop/Amp High
500 kcmil253.4 mm²380 A10.94 V (4.56%)229.1 V18.05 V (7.52%)4649.4 WDrop/Amp High
600 kcmil304.0 mm²420 A9.12 V (3.8%)230.9 V15.04 V (6.27%)3875.5 WDrop/Amp High
750 kcmil380.0 mm²475 A7.3 V (3.04%)232.7 V12.03 V (5.01%)3100.4 W~ ≤5%
1000 kcmil506.7 mm²545 A5.47 V (2.28%)234.5 V9.02 V (3.76%)2325.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 500 feet one-way at 240V (1-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 5.47V (2.28%) and delivers 234.5V at the load.

What size aluminum wire is required for 425 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.02V (3.76%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.